Sub-Chart A-1: Induction Motor Auto-Tuning And Test Run Procedure - YASKAWA GA700 Series Technical Manual

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

4.4 Start-up Procedures

Sub-Chart A-1: Induction Motor Auto-Tuning and Test Run Procedure

*1
When A1-02 = 4 [Control Method Selection = AOLV], If you operate the drive at a frequency lower than n4-70 [Speed Command
Comp @ Low Freq] (default setting: 1.00 Hz), the motor can rotate at a frequency about 1/2 of n4-70. When you do a test run, set
E1-09 > 0 [Minimum Output Frequency > 0]. The recommended setting for E1-09 is 0.5 Hz.
*2
Be sure to release the holding brake before doing Inertia Tuning.
*3
In ASR Tuning, the drive will automatically tune Feed Forward control and KEB Ride-Thru 2 parameters.
144
Figure 4.9 Induction Motor Auto-Tuning and Test Run Procedure
YASKAWA SIEPC71061705H GA700 Series Technical Manual