7.10 Troubleshooting Without Fault Display
Causes
L3-01 = 3 [Stall Prevent Select duringAccel = ILim Mode] has been set.
The motor is rotating at this speed:
b2-01 [DC Injection/Zero SpeedThreshold] ≤ Motor Speed < E1-09
[Minimum Output Frequency]

The Motor Is Making an Audible Noise

Causes
100% of the rated output current of the drive was exceeded while operating
at low speeds.

The Motor Will Not Restart after a Loss of Power

Causes
The drive did not receive a Run command after applying power.
For applications that use 3-wire sequence, the momentary power loss
continued for a long time, and the relay that keeps the Run command has
been switched off.
380
Possible Solutions
1.
Check whether the V/f pattern and motor parameter settings are appropriate, and set them
correctly.
2.
If this does not solve the problem, and it is not necessary to limit the current level of stall
during acceleration, adjust L3-02.
3.
If this does not solve the problem, set L3-01 = 1 [Enabled].
• Set b1-21 = 1 [CLV Start Selection = Accept Run command at any speed].
• Set E1-09 < b2-01.
Possible Solutions
• If the sound is coming from the motor, set L8-38 = 0 [Carrier Frequency Reduction =
Disabled].
• If oL2 [Drive Overloaded] occurs frequently after setting L8-38 = 0, replace the drive with a
high-capacity drive.
Possible Solutions
• Examine the sequence and wiring that enters the Run command.
• Set up a relay to make sure that the Run command stays enabled during a loss of power.
Examine the wiring and circuitry for the relay that keeps the Run command enabled during the
momentary power loss ride-thru time.
YASKAWA SIEPC71061705H GA700 Series Technical Manual