12.6 E: Motor Parameters
E5-24: PM Back-EMF L-L Vrms (mV/rpm)
No.
Name
(Hex.)
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
(0353)
Set this parameter when you use an SPM motor.
PM motor Auto-Tuning automatically sets this parameter to the value of [Back-EMF Voltage Constant (Ke)].
When E5-01 = FFFF, only set E5-09 [PM Back-EMF Vpeak (mV/(rad/s))] or E5-24 as the induced voltage
constant.
Note:
When you set this parameter, also set E5-09 = 0.0. The drive will detect oPE08 [Parameter Selection Error] in these conditions:
• E5-09 = 0.0 and E5-24 = 0.0
• E5-09 ≠ 0.0 and E5-24 ≠ 0.0
E5-25: Polarity Estimation Timeout
No.
Name
(Hex.)
E5-25
Polarity Estimation Timeout
(035E)
Expert
0 : Disabled
1 : Enabled

E9: Motor Setting

E9 parameters are used to configure induction motors, PM motors, and SynRM motors. Configure these
parameters only for derating torque applications in which a high level of responsiveness and accurate speed
control are not required.
E9 parameters are automatically configured with values input by the Auto-Tuning process for motor parameter
settings. E9 parameters can be manually configured when the EZ Tuning process cannot be performed.
E9-01: Motor Type Selection
No.
Name
(Hex.)
E9-01
Motor Type Selection
(11E4)
EZ Tuning automatically sets this parameter to the value of [Motor Type Selection].
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
E9-02: Maximum Speed
No.
Name
(Hex.)
E9-02
Maximum Speed
(11E5)
Note:
The unit of measure changes when the setting of o1-04 [V/f Pattern Display Unit].
EZ Tuning automatically sets this parameter to the value of [Motor Max Revolutions].
756
V/f
CL-V/f
OLV
CLV
AOLV
Sets the RMS value for PM motor line voltage.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that switches polarity for initial polarity estimation. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum speed of the motor.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
200 V Class:
-1
100.0 mV/min
400 V Class:
-1
200.0 mV/min
-1
(0.0 - 6500.0 mV/min
)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 2)
Default
(Range)
Determined by E9-01
(40.0 - 120.0 Hz)