YASKAWA GA700 Series Technical Manual page 804

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

12.8 H: Terminal Functions
Note:
• To input the Run command, activate the terminal for 1 ms minimum.
• The default setting for b1-17 [Run Command at Power Up] is 0 [Disregard existing RUN command]. If you enable the Run command
on an energized drive, the protective function activates and the
Run, set b1-17 = 1 [Accept Existing RUN Command].
1: LOCAL/REMOTE Selection
Setting Value
Function
1
LOCAL/REMOTE
Selection
Note:
• When the MFDI terminal sets the LOCAL/REMOTE selection,
• When LOCAL Mode is selected, the green light for
• When the Run command is ON, you cannot switch between LOCAL Mode and REMOTE Mode.
ON : LOCAL
The keypad is the Frequency reference source and Run command source.
OFF : REMOTE
The frequency reference and Run command settings are set in b1-01, b1-02 [Frequency Reference Selection 1/2]
or b1-15, b1-16 [Run Command Selection 1/2].
2: External Reference 1/2 Selection
Setting Value
Function
2
External Reference 1/2
Selection
Note:
When the drive is receiving a Run command, you cannot switch between reference sources.
ON : b1-15 [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF : b1-01 [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
3: Multi-Step Speed Reference 1
Setting Value
Function
3
Multi-Step Speed Reference
1
Note:
Refer to
Setting Procedures for Multi-step Speed Operation on page 717
4: Multi-Step Speed Reference 2
Setting Value
Function
4
Multi-Step Speed Reference
2
Note:
Refer to
Setting Procedures for Multi-step Speed Operation on page 717
5: Multi-Step Speed Reference 3
Setting Value
Function
5
Multi-Step Speed Reference
3
Note:
Refer to
Setting Procedures for Multi-step Speed Operation on page 717
804
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
comes on.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
CL-V/f
OLV
CLV
AOLV
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
V/f
CL-V/f
OLV
CLV
AOLV
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
flashes quickly. When the application will let an energized drive
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
on the keypad is disabled.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
for more information.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
for more information.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
for more information.
YASKAWA SIEPC71061705H GA700 Series Technical Manual