12.2 A: Initialization Parameters
No.
A1-02
b1-04
C6-01
E1-03
E1-07
E1-08
L2-01
L3-04
The drive saves the parameters in
Table 12.9 Parameters Saved as User Parameters with the Exhaust Fan Preset
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
A2-08
A2-09
A2-10
A2-11
A2-12
A2-13
A2-14
4 : HVAC Fan
The drive automatically sets the parameters in
No.
A1-02
b1-04
b1-17
C6-01
C6-02
H2-03
L2-01
L8-03
L8-38
The drive saves the parameters in
Table 12.11 Parameters Saved as User Parameters with the HVAC Preset
User Parameter No.
A2-01
A2-02
A2-03
628
Table 12.8 Best Parameter Settings for Exhaust Fan Applications
Control Method Selection
Reverse Operation Selection
Normal / Heavy Duty Selection
Mid Point A Frequency
Power Loss Ride Through Select
Stall Prevention during Decel
Table 12.9
as user parameters.
Parameter No. Saved
Table 12.10
Table 12.10 Best Parameter Settings for HVAC Applications
Control Method Selection
Reverse Operation Selection
Run Command at Power Up
Normal / Heavy Duty Selection
Carrier Frequency Selection
Terminal M5-M6 Function Selection
Power Loss Ride Through Select
Overheat Pre-Alarm Selection
Carrier Frequency Reduction
Table 12.11
as user parameters.
Parameter No. Saved
Name
V/f Pattern Selection
Mid Point A Voltage
b1-01
b1-02
b1-04
b3-01
C1-01
C1-02
E1-03
E1-07
E1-08
E2-01
H1-05
H1-06
H1-07
L5-01
for an HVAC fan application.
Name
b1-01
b1-02
b1-03
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Optimal Value
0: V/f Control
1: Reverse Disabled
1: Normal Duty Rating
F: Custom
30.0 Hz
50.0 V
1: Enabled
1: Enabled
Name
Frequency Reference Selection 1
Run Command Selection 1
Reverse Operation Selection
Speed Search at Start Selection
Acceleration Time 1
Deceleration Time 1
V/f Pattern Selection
Mid Point A Frequency
Mid Point A Voltage
Motor Rated Current (FLA)
Terminal S5 Function Selection
Terminal S6 Function Selection
Terminal S7 Function Selection
Number of Auto-Restart Attempts
Optimal Value
0: V/f Control
1: Reverse Disabled
1: Accept Existing RUN Command
1: Normal Duty Rating
3: 8.0 kHz
39: Watt Hour Pulse Output
2: Enabled while CPU Power Active
4: Operate at Reduced Speed (L8-19)
2: Enabled for All Speeds
Name
Frequency Reference Selection 1
Run Command Selection 1
Stopping Method Selection