18: Timer Function
Setting Value
Function
18
Timer Function
Note:
Refer to "b4: Timer Function" for more information.
19: PID Disable
Setting Value
Function
19
PID Disable
ON : PID control disabled
OFF : PID control enabled
1A: Accel/Decel Time Selection 2
Setting Value
Function
1A
Accel/Decel Time Selection
2
Note:
Refer to
C1: Accel & Decel Time on page 692
1B: Programming Lockout
Setting Value
Function
1B
Programming Lockout
You can continue to view parameter setting values when the terminal is OFF [Parameter Write Prohibit].
ON : Programming Lockout
OFF : Parameter Write Prohibit
1E: Reference Sample Hold
Setting Value
Function
1E
Reference Sample Hold
When the terminal is active for 100 ms, this function reads a sample of the analog frequency reference and holds
that sample. When you input the sample/hold command again, the function reads a sample of the analog
frequency reference again and holds that sample. When you turn off the power, the drive erases the saved analog
frequency and resets the frequency reference to 0.
Figure 12.86
shows an example of how the function operates.
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Figure 12.85 Fast Stop Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable PID control when b5-01 = 1 to 8 [PID Mode Setting = Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and H1-xx = 7 [Accel/Decel Time Selection 1] together. Sets the drive to use Acceleration/Deceleration Time 3
[C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to prevent parameter changes when the terminal is OFF.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to sample the frequency reference at terminals A1, A2, or A3 and hold the frequency reference at that
frequency.
12.8 H: Terminal Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12
811