12.9 L: Protection Functions
L8-12: Ambient Temperature Setting
No.
Name
(Hex.)
L8-12
Ambient Temperature
Setting
(04B8)
The drive automatically adjusts the drive rated current to the best value as specified by the set temperature. Set the
ambient temperature of the area where you install the drive to a value that is more than the drive rating.
Refer to
Derating Depending on Ambient Temperature on page 444
ambient temperature.
L8-15: Drive oL2 @ Low Speed Protection
No.
Name
(Hex.)
L8-15
Drive oL2 @ Low Speed
Protection
(04BB)
Note:
Contact Yaskawa or your nearest sales representative before disabling this function at low speeds. If you frequently operate drives with
high output current in low speed ranges, it can cause heat stress and decrease the life span of drive IGBTs.
0 : Disabled (No Additional Derate)
The drive does not decrease the overload protection level.
1 : Enabled (Reduced oL2 Level)
When the drive detects oL2 during low speed operation, it automatically decreases the overload detection level.
At zero speed, the drive derates the overload by 50%.
L8-18: Software Current Limit Selection
No.
Name
(Hex.)
L8-18
Software Current Limit
Selection
(04BE)
0 : Disabled
When the output current is at the software current limit value, the drive does not restrict the output voltage.
Note:
The drive may detect an oC [Overcurrent] when loads are particularly heavy or the acceleration time is particularly short.
1 : Enabled
When the output current is at the software current limit value, the drive decreases output voltage to decrease
output current.
When the output current decreases to the software current limit level, the drive starts usual operation.
L8-19: Freq Reduction @ oH Pre-Alarm
No.
Name
(Hex.)
L8-19
Freq Reduction @ oH Pre-
Alarm
(04BF)
When these two conditions are correct, this function is enabled:
• L8-03 = 4 [Overheat Pre-Alarm Ope Selection = Run@L8-19 Rate]
• oH alarm is output
912
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ambient temperature of the drive installation area.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to decrease the drive overload level at which the drive will trigger oL2 [Drive
Overload] during low speed operation (6 Hz or slower) to prevent damage to the main circuit
transistors.
V/f
CL-V/f
OLV
CLV
AOLV
Set the software current limit selection function to prevent damage to the main circuit transistor
caused by too much current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio at which the drive derates the frequency reference during an oH alarm.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
for information about derating depending on
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
40 °C
(-10 °C - +50 °C)
Default
(Range)
1
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0.8
(0.1 - 0.9)