Setting Value
Function
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
16
Motor 2 Selection
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1A
Accel/Decel Time
Selection 2
1B
Programming Lockout
1E
Reference Sample Hold
20
External Fault (NO-
Always-Ramp)
21
External Fault (NC-
Always-Ramp)
22
External Fault (NO-
@Run-Ramp)
23
External Fault (NC-
@Run-Ramp)
24
External Fault (NO-
Always-Coast)
25
External Fault (NC-
Always-Coast)
26
External Fault (NO-
@Run-Coast)
27
External Fault (NC-
@Run-Coast)
28
External Fault (NO-
Always-FStop)
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to operate the motor in the reverse direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command
before trying to reset a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
ON while the drive is operating.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
ON : Selects motor 2
OFF : Selects motor 1
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
ON while the drive is operating.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable PID control when b5-01 = 1 to 8 [PID Mode Setting = Enabled].
ON : PID control disabled
OFF : PID control enabled
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and H1-xx = 7 [Accel/Decel Time Selection 1] together. Sets the drive to use Acceleration/
Deceleration Time 3 [C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to sample the frequency reference at terminals A1, A2, or A3 and hold the frequency reference
at that frequency.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is
stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is
stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates during run, the drive ramps to stop in the selected deceleration time. Fault relay output
terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the
drive is stopped.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates during run, the drive ramps to stop in the selected deceleration time. Fault relay
output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while
the drive is stopped.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is
stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates, the drive shuts off the output and the motor coasts to stop. Fault relay output
terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the
drive is stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates during run, the drive shuts off the output and the motor coasts to stop. Fault relay
output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while
the drive is stopped.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates during run, the drive shuts off the output and the motor coasts to stop. Fault relay
output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while
the drive is stopped.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop Time]. Fault
relay output terminal MA-MC turns ON, and MB-MC turns OFF. Stopped drives and running drives will detect
external faults.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.10 H: Terminal Functions
Ref.
809
809
809
809
810
811
811
811
811
811
812
812
812
812
812
812
812
812
812