YASKAWA GA700 Series Technical Manual page 916

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

12.9 L: Protection Functions
L8-52: STPo Integration Level
No.
Name
(Hex.)
L8-52
STPo Integration Level
(0472)
Expert
L8-53: STPo Integration Time
No.
Name
(Hex.)
L8-53
STPo Integration Time
(0473)
Expert
L8-54: STPo Id Diff Detection
No.
Name
(Hex.)
L8-54
STPo Id Diff Detection
(0474)
Expert
0 : Disabled
1 : Enabled
L8-55: Internal DB TransistorProtection
No.
Name
(Hex.)
L8-55
Internal DB
TransistorProtection
(045F)
0 : Disable
Disables braking transistor protection.
Use this setting, if enabling the braking transistor can cause an rF [Braking Resistor Fault] in these conditions:
• With a regenerative converter, for example D1000.
• With a regenerative unit, for example R1000.
• When connecting braking resistor options to the drive, for example CDBR units.
• Without an internal braking transistor.
1 : Protection Enabled
Protects internal braking transistor when using a braking transistor or optional braking resistors.
These models have a built-in braking transistor:
• 2004 to 2138
• 4002 to 4168
L8-56: Stall P @ Accel Activation Time
No.
Name
(Hex.)
L8-56
Stall P @ Accel Activation
Time
(047D)
Expert
Note:
If this value is too small, it can cause incorrect detection of STPo. If this value is too large, the drive will not detect STPo.
916
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for STPo [Motor Step-Out Detected] related to the ACR integral value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the drive detects STPo after it is more than the value of L8-51 [STPo I
Detection Level].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Id deviation detection function for STPo [Motor Step-Out Detected].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the protection function for the internal braking transistor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length time that the acceleration stall prevention function can continue to operate before
the drive detects an STPo [Motor Step-Out Detected].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
1.0
(0.1 - 2.0)
Default
(Range)
1.0 s
(1.0 - 10.0 s)
Default
(Range)
1
(0, 1)
Default
(Range)
1
(0, 1)
Default
(Range)
5000 ms
(100 - 5000 ms)

Advertisement

Table of Contents
loading

Table of Contents