n5-01: Feed Forward Control Selection
No.
Name
(Hex.)
n5-01
Feed Forward Control
Selection
(05B0)
0 : Disabled
1 : Enabled
n5-02: Motor Inertia Acceleration Time
No.
Name
(Hex.)
n5-02
Motor Inertia Acceleration
Time
(05B1)
If you cannot do Inertia Tuning, calculate the motor acceleration time as shown here or measure the motor
acceleration time and set n5-02 to this value.
Calculate the Motor Acceleration Time
Use this formula to find the motor acceleration time:
• J
= Moment of inertia of motor (kg m
Motor
• n
= Motor rated speed (min
rated
• T
= Motor rated torque (N m)
rated
You can also use this formula to find the motor acceleration time:
• f
= Motor rated frequency (Hz)
rated
• P = Number of motor poles
Calculate the Motor Acceleration Time
Use this procedure to calculate the motor acceleration time:
1. Use A1-02 [Control Method Selection] to set the control method.
2. Disconnect the motor and load.
3. Run Auto-Tuning to set motor parameters.
When you cannot do Auto-Tuning, manually set motor parameters with the information on the motor
nameplate or test reports. Set the E2 parameters for induction motors. Set the E5 parameters for PM motors.
4. Set C5 parameters [Automatic Speed Regulator (ASR)].
5. Set C1-01 [Acceleration Time 1] = 0.
6. Set L7-01 [Forward Torque Limit] to 100%.
7. Set the frequency reference to the same value as the motor rated speed.
8. Measure the length of time for the motor to reach the rated speed.
Show U1-05 [Motor Speed] on the keypad and enter the Run command (forward run).
9. Stop the motor.
10. Set n5-02 to the measured motor acceleration time value.
Reset all of the parameters that you changed to the previous setting values.
n5-03: Feed Forward Control Gain
No.
Name
(Hex.)
n5-03
Feed Forward Control Gain
(05B2)
When you cannot do Inertia Tuning, use this procedure to set n5-03:
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the feed forward function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time for the motor to accelerate from the stopped to the maximum frequency
with a single motor at the rated torque. Inertia Tuning automatically sets the motor acceleration
time.
2
)
-1
, r/min)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio between load inertia and motor inertia. Inertia Tuning automatically sets the
Feedforward Control Gain value.
12.10 n: Special Adjustment
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0, 1)
Default
(Range)
Determined by C6-01, E5-
01, and o2-04
(0.001 - 10.000 s)
Default
(Range)
1.00
(0.00 - 100.00)
12
929