H3: Analog Inputs - YASKAWA GA700 Series Technical Manual

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

H3: Analog Inputs

No.
Name
(Hex.)
H3-01
Terminal A1 Signal
Level Select
(0410)
H3-02
Terminal A1 Function
Selection
(0434)
H3-03
Terminal A1 Gain
Setting
(0411)
RUN
H3-04
Terminal A1 Bias
Setting
(0412)
RUN
H3-05
Terminal A3 Signal
Level Select
(0413)
H3-06
Terminal A3 Function
Selection
(0414)
H3-07
Terminal A3 Gain
Setting
(0415)
RUN
H3-08
Terminal A3 Bias
Setting
(0416)
RUN
H3-09
Terminal A2 Signal
Level Select
(0417)
H3-10
Terminal A2 Function
Selection
(0418)
H3-11
Terminal A2 Gain
Setting
(0419)
RUN
H3-12
Terminal A2 Bias
Setting
(041A)
RUN
H3-13
Analog Input FilterTime
Constant
(041B)
H3-14
Analog Input Terminal
Enable Sel
(041C)
H3-16
Terminal A1 Offset
(02F0)
H3-17
Terminal A2 Offset
(02F1)
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A1.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A3.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFAI terminal A3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant for primary delay filters on MFAI terminals.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select =
Analog Terminal Enable Selection] is ON.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary
to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary
to change this setting.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.10 H: Terminal Functions
Default
Ref.
(Range)
0
846
(0 - 3)
0
847
(0 - 32)
100.0%
847
(-999.9 - +999.9%)
0.0%
847
(-999.9 - +999.9%)
0
847
(0 - 3)
2
848
(0 - 32)
100.0%
848
(-999.9 - +999.9%)
0.0%
848
(-999.9 - +999.9%)
2
848
(0 - 3)
0
849
(0 - 32)
100.0%
849
(-999.9 - +999.9%)
0.0%
849
(-999.9 - +999.9%)
0.03 s
849
(0.00 - 2.00 s)
7
849
(1 - 7)
0
850
(-500 - +500)
0
850
(-500 - +500)
11
541

Advertisement

Table of Contents
loading

Table of Contents