C: Tuning; C1: Accel & Decel Time; C2: S-Curve Characteristics - YASKAWA GA700 Series Technical Manual

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

11.6 C: Tuning

11.6
C: Tuning
C1: Accel & Decel Time
No.
Name
(Hex.)
C1-01
Acceleration Time 1
(0200)
RUN
C1-02
Deceleration Time 1
(0201)
RUN
C1-03
Acceleration Time 2
(0202)
RUN
C1-04
Deceleration Time 2
(0203)
RUN
C1-05
Acceleration Time 3
(0204)
RUN
C1-06
Deceleration Time 3
(0205)
RUN
C1-07
Acceleration Time 4
(0206)
RUN
C1-08
Deceleration Time 4
(0207)
RUN
C1-09
Fast Stop Time
(0208)
RUN
C1-10
Accel/Decel Time
Setting Units
(0209)
C1-11
Accel/Decel Time
Switching Frequency
(020A)
C1-14
Accel/Decel Rate
Frequency
(0264)
RUN

C2: S-Curve Characteristics

No.
Name
(Hex.)
C2-01
S-Curve Time @ Start of
Accel
(020B)
C2-02
S-Curve Time @ End of
Accel
(020C)
C2-03
S-Curve Time @ Start of
Decel
(020D)
C2-04
S-Curve Time @ End of
Decel
(020E)
492
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Note:
• Decelerating too quickly can cause an ov [Overvoltage] fault that shuts off the
drive while the motor to coasts to a stop. Set a Fast Stop time in C1-09 that
prevents motor coasting and makes sure that the motor stops quickly and safely.
• When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru
1] and you do KEB Auto-Tuning, the drive will automatically set C1-09. If you
must not change the Fast Stop time, do not do KEB Tuning.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the setting units for C1-01 to C1-08 [Accel/Decel Times 1 to 4], C1-09 [Fast Stop
Time], L2-06 [Kinetic Energy Backup Decel Time], and L2-07 [Kinetic Energy Backup
Accel Time].
0 : 0.01 s (0.00 to 600.00 s)
1 : 0.1 s (0.0 to 6000.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency at which the drive will automatically change acceleration and
deceleration times.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base frequency used to calculate acceleration and deceleration rates.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the S-curve acceleration time at start.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the S-curve acceleration time at completion.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the S-curve deceleration time at start.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the S-curve deceleration time at completion.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
Ref.
(Range)
10.0 s
693
(0.0 - 6000.0 s)
10.0 s
694
(0.0 - 6000.0 s)
10.0 s
694
(0.0 - 6000.0 s)
10.0 s
694
(0.0 - 6000.0 s)
10.0 s
694
(0.0 - 6000.0 s)
10.0 s
694
(0.0 - 6000.0 s)
10.0 s
694
(0.0 - 6000.0 s)
10.0 s
695
(0.0 - 6000.0 s)
10.0 s
695
(0.0 - 6000.0 s)
1
695
(0, 1)
Determined by A1-02
695
(0.0 - 590.0 Hz)
0.0 Hz
696
(0.0 - 590.0 Hz)
Default
Ref.
(Range)
Determined by A1-02
698
(0.00 - 10.00 s)
0.20 s
698
(0.00 - 10.00 s)
0.20 s
698
(0.00 - 10.00 s)
0.00 s
698
(0.00 - 10.00 s)

Advertisement

Table of Contents
loading

Table of Contents