(Hex.)
U1-10 [Input Terminal Status]
bit 0
bit 1
bit 2
bit 3
002B
bit 4
bit 5
bit 6
bit 7
bit 8 - F
Drive Status 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
002C
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
U1-11 [Output Terminal Status]
bit 0
bit 1
002D
bit 2
bit 3 - 6
bit 7
bit 8 - F
002E
Reserved
YASKAWA SIEPC71061705H GA700 Series Technical Manual
1: Control circuit terminal S1 ON
1: Control circuit terminal S2 ON
1: Control circuit terminal S3 ON
1: Control circuit terminal S4 ON
1: Control circuit terminal S5 ON
1: Control circuit terminal S6 ON
1: Control circuit terminal S7 ON
1: Control circuit terminal S8 ON
Reserved
During Run
1: During Run
During zero speed
1: During zero speed
Speed agreement
1: During agreement
User-defined speed agreement
1: During agreement
Frequency Detection 1
1: Output frequency ≤ L4-01
Frequency Detection 2
1: Output frequency ≥ L4-01
Drive ready
1: Run ready
During low voltage detection
1: During detection
During baseblock
1: Drive output during baseblock
Frequency reference mode
1: No communication option, 0: Communication option
Run command mode
1: No communication option, 0: Communication option
During overtorque/undertorque 1, 2 detection
Frequency reference loss
1: Loss
Executing Auto-Restart
1: Restart Enabled
Fault
1: Fault generated
MEMOBUS/Modbus communications timeout
1: At Timeout
MFDO (terminal M1-M2)
1: ON, 0: OFF
MFDO (terminal M3-M4)
1: ON, 0: OFF
MFDO (terminal M5-M6)
1: ON, 0: OFF
Reserved
Fault relay output (terminal MA/MB-MC)
1: ON, 0: OFF
Reserved
6.3 MEMOBUS/Modbus Communications