◼ o5 -00: Log Type
No.
Name
( Hex.)
o5-00
Logging Type
(1E81)
Selection
RUN
0 : Long Term L og
Saves data continuously over a long time period.
1 : Short Term L og
Saves data of a certain time period before and after the detection of a trigger with a short
sampling cycle.
◼ o5 -01: Log Start/Stop Selection
No.
Name
( Hex.)
o5-01
Log Start/Stop
(1551)
Selection
RUN
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in
◼ o5 -02: Log Sampling I nterval
No.
Name
( Hex.)
o5-02
Log Sampling
(1552)
Interval
RUN
◼ o5 -03: Log Monitor D ata 1
No.
Name
( Hex.)
o5-03
Log Monitor Data
(1553)
1
RUN
Note: Set the
U monitor
For example, to display
not necessary to set a data log monitor, set this parameter to
4
Log monitor data (Hex.) of the monitor selected with
4
Log monitor data (Hex.) of the monitor selected with
:
:
4
Log monitor data (Hex.) of the monitor selected with
4
-
4
Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 through 10. A bit value
of 1 shows that the data represents a negative value. (Log monitor data 1
through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7
have values of 1, and the encoding data = 0010010010 (Bin.) = 0092 (Hex.)
6
Row number (Hex.) in the data log file
V / f
C L - V / f
O LV
Selects the type of data log function. This parameter is
only available when using an LCD keypad.
V / f
C L - V / f
O LV
Sets the data log function. This parameter is only
available when using an LCD keypad.
V / f
C L - V / f
O LV
Sets the data log sampling cycle. This parameter is only
available when using an LCD keypad.
V / f
C L - V / f
O LV
Sets the data log monitor. This parameter is only
available when using an LCD keypad.
number you will log.
U1-01 [Frequency Reference]
De scription
De scription
CLV A OLV O L V / P M
A O L V / P M C L V / P M
De scription
CLV A OLV O L V / P M
A O L V / P M C L V / P M
o5-02 [Log Sampling Interval]
De scription
CLV A OLV O L V / P M
A O L V / P M C L V / P M
De scription
CLV A OLV O L V / P M
A O L V / P M C L V / P M
, set
o5-03 [Log Monitor Data 1]
o5-04 [Log Monitor Data 2]
o5-12 [Log Monitor Data 10]
De fault
( Range)
0
E Z O L V
(0 - 1)
De fault
( Range)
0
E Z O L V
(0 - 1)
De fault
( Range)
1000 ms
E Z O L V
when
o5-00 = 0,
o5-00 = 1
10 ms when
(0 - 6000 ms)
De fault
( Range)
101
E Z O L V
(000,101 - 999)
o5-03 = 101
. When it is
000
.