12.9 L: Protection Functions
L3-39: Current Limit Filter Time @Accel
No.
Name
(Hex.)
L3-39
Current Limit Filter Time
@Accel
(11D3)
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.
L3-40: Current Limit S-Curve @ Acc/Dec
No.
Name
(Hex.)
L3-40
Current Limit S-Curve @
Acc/Dec
(11D4)
Makes the best motor acceleration rate for start up. If you set this parameter to 1, it will make acceleration
smoother, but it can also increase the acceleration time to be longer than the set time. If the drive detects oC
[Overcurrent] faults immediately after acceleration starts, set this parameter.
0 : Disable
1 : Enabled
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.

L4: Speed Detection

L4 parameters set the output of signals to the MFDO terminals, for example frequency agree and speed detection.
The drive detects motor speed in CLV or CLV/PM control methods.
L4-01: Speed Agree Detection Level
No.
Name
(Hex.)
L4-01
Speed Agree Detection
Level
(0499)
Sets the level to detect speed agree or motor speed when H2-01 to H2-03 = 2, 3, 4, 5 [MFDO Function Select =
Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2].
L4-02: Speed Agree Detection Width
No.
Name
(Hex.)
L4-02
Speed Agree Detection
Width
(049A)
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = 2, 3, 4, 5 [MFDO Function Select =
Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2].
L4-03: Speed Agree Detection Level (+/-)
No.
Name
(Hex.)
L4-03
Speed Agree Detection
Level (+/-)
(049B)
Sets the speed agree detection level or motor speed detection level when H2-01 to H2-03 = 13, 14, 15, 16 [MFDO
Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4].
896
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to adjust the acceleration rate when L3-01 = 3 [Stall Prevention during
Accel = Current Limit Method]. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable and disable the best S-curve characteristic used for current-limited
acceleration.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to detect speed agree or motor speed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width to detect speed agree or motor speed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to detect speed agree or motor speed.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
100.0 ms
(1.0 - 1000.0 ms)
Default
(Range)
0
(0, 1)
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Default
(Range)
Determined by A1-02
(Determined by A1-02)