H3-10: Terminal A2 Function Selection
No.
Name
(Hex.)
H3-10
Terminal A2 Function
Selection
(0418)
H3-11: Terminal A2 Gain Setting
No.
Name
(Hex.)
H3-11
Terminal A2 Gain Setting
(0419)
RUN
When 10 V (or 20 mA) is input, this parameter sets the reference quantity for the function set for terminal A2 as a
percentage.
Use this parameter and H3-12 [Terminal A2 Bias Setting] to adjust the characteristics of the analog input signal to
terminal A2.
H3-12: Terminal A2 Bias Setting
No.
Name
(Hex.)
H3-12
Terminal A2 Bias Setting
(041A)
RUN
When 0 V (4 mA or 0 mA) is input, this parameter sets the bias for the function set for terminal A2 as a
percentage.
Use this parameter and H3-11 [Terminal A2 Gain Setting] to adjust the characteristics of the analog input signal to
terminal A2.
H3-13: Analog Input FilterTime Constant
No.
Name
(Hex.)
H3-13
Analog Input FilterTime
Constant
(041B)
Apply the primary delay filter to the analog input to enable an analog input signal without the use of high-
frequency noise components. An analog input filter prevents irregular drive control. Drive operation becomes
more stable as the programmed time becomes longer, but it also becomes less responsive to quickly changing
analog signals.
H3-14: Analog Input Terminal Enable Sel
No.
Name
(Hex.)
H3-14
Analog Input Terminal
Enable Sel
(041C)
Input signals do not have an effect on terminals not set as targets.
1 : Terminal A1
2 : Terminal A2
3 : Terminals A1 and A2
4 : Terminal A3
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant for primary delay filters on MFAI terminals.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog
Terminal Enable Selection] is ON.
12.8 H: Terminal Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0 - 32)
Default
(Range)
100.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0.03 s
(0.00 - 2.00 s)
Default
(Range)
7
(1 - 7)
12
849