YASKAWA GA700 Series Technical Manual page 949

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

To start the drive again after you push
again.
o2-03: User Parameter Default Value
No.
Name
(Hex.)
o2-03
User Parameter Default
Value
(0507)
When you set o2-03 = 1 [Set defaults], the drive saves changed parameter settings as user parameter setting
values in a part of the memory that is isolated from drive parameters.
When you set A1-03 = 1110 [Initialize Parameters = User Initialization] to initialize the drive, the drive resets the
internal parameter setting values to those user parameter setting values.
0 : No change
1 : Set defaults
Saves changed parameter setting values as user default settings.
Set o2-03 = 1 then push
03 automatically resets to 0.
2 : Clear all
Deletes all of the saved user parameter setting values.
Set o2-03 = 2 then push
0. If you delete the user parameter setting values, you cannot set A1-03 = 1110 to initialize parameters.
o2-04: Drive Model (KVA) Selection
No.
Name
(Hex.)
o2-04
Drive Model (KVA)
Selection
(0508)
NOTICE: Set o2-04 [Drive Model (KVA) Selection] correctly. If you set this parameter incorrectly, it will decrease drive
performance, cause the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of o2-04 changes, related parameter setting values also change. Refer to
Rating ND/HD on page 602
These tables list the relation between o2-04 setting values and drive models.
Drive Model
2004
2006
2010
2012
2018
2021
2030
2042
2056
2070
Drive Model
4002
4004
YASKAWA SIEPC71061705H GA700 Series Technical Manual
to stop operation, turn the external Run command OFF and ON
V/f
CL-V/f
OLV
CLV
Sets the function to keep the settings of changed parameters as user parameter defaults to use
during initialization.
to save the user parameter setting values. After the drive saves the setting value, o2-
to clear the user parameter setting values. The drive will automatically reset o2-03 to
V/f
CL-V/f
OLV
CLV
Sets the Drive Model code. Set this parameter after replacing the control board.
for more information.
Table 12.79 Three-Phase 200 V Class
o2-04 Setting
62
63
65
66
67
68
6A
6B
6D
6E
Table 12.80 Three-Phase 400 V Class
o2-04 Setting
92
93
12.11 o: Keypad-Related Settings
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Drive Model
2082
2110
2138
2169
2211
2257
2313
2360
2415
Drive Model
4005
4007
Default
(Range)
0
(0 - 2)
Default
(Range)
Determined by the drive
(-)
Defaults by Drive Model and Duty
o2-04 Setting
6F
70
72
73
74
75
76
77
78
o2-04 Setting
94
95
12
949