H2-07: Modbus Register 1 Address Select
No.
Name
(Hex.)
H2-07
Modbus Register 1 Address
Select
(0B3A)
Sets the address of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the
bit in H2-08 [Modbus Register 1 Bit Select].
H2-08: Modbus Register 1 Bit Select
No.
Name
(Hex.)
H2-08
Modbus Register 1 Bit
Select
(0B3B)
Sets the bit of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the
address in H2-07 [Modbus Register 1 Address Select].
H2-09: Modbus Register 2 Address Select
No.
Name
(Hex.)
H2-09
Modbus Register 2 Address
Select
(0B3C)
Sets H2-09 with the address of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63]
and uses the bit in H2-10 [Modbus Register 2 Bit Select].
H2-10: Modbus Register 2 Bit Select
No.
Name
(Hex.)
H2-10
Modbus Register 2 Bit
Select
(0B3D)
Sets the bit of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and uses the
address in H2-09.
H2-20: Comparator 1 Monitor Selection
No.
Name
(Hex.)
H2-20
Comparator 1 Monitor
Selection
(1540)
Note:
• For information on the comparator function, refer to
• The configurable monitor changes when the control method changes.
H2-21: Comparator 1 Lower Limit
No.
Name
(Hex.)
H2-21
Comparator 1 Lower Limit
(1541)
Note:
For information on the comparator function, refer to
H2-22: Comparator 1 Upper Limit
No.
Name
(Hex.)
H2-22
Comparator 1 Upper Limit
(1542)
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example,
set H2-20 = 102 to monitor U1-02 [Output Frequency].
66: Comparator1 on page 843
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
66: Comparator1 on page 843
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
12.8 H: Terminal Functions
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
and
67: Comparator2 on page
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
and
67: Comparator2 on page
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0001
(0001 - 1FFF)
Default
(Range)
0000
(0000 - FFFF)
Default
(Range)
0001
(0001 - 1FFF)
Default
(Range)
0000
(0000 - FFFF)
Default
(Range)
102
(000 - 999)
843.
Default
(Range)
0.0%
(0.0 - 300.0%)
843.
Default
(Range)
0.0%
(0.0 - 300.0%)
12
825