11.11 L: Protection Functions
No.
Name
(Hex.)
L6-04
Torque Detection
Selection 2
(04A4)
L6-05
Torque Detection Level
2
(04A5)
L6-06
Torque Detection Time 2
(04A6)
L6-07
Torque Detection Filter
Time
(04E5)
L6-08
Mechanical Fatigue
Detect Select
(0468)
L6-09
Mech Fatigue Detect
Speed Level
(0469)
L6-10
Mech Fatigue Detect
Delay Time
(046A)
L6-11
Mech Fatigue Hold Off
Time
(046B)

L7: Torque Limit

No.
Name
(Hex.)
L7-01
Forward Torque Limit
(04A7)
RUN
L7-02
Reverse Torque Limit
(04A8)
RUN
L7-03
Forward Regenerative
Trq Limit
(04A9)
RUN
L7-04
Reverse Regenerative
Trq Limit
(04AA)
RUN
L7-06
Torque Limit Integral
Time
(04AC)
554
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive
rated output current = 100% value. In vector control, motor rated torque = 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for Overtorque/Undertorque Detection 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant for a primary filter to the torque reference or to the output current
used to detect overtorque/undertorque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed where the drive detects mechanical deterioration and how the drive
operates (operation status) after detection.
0 : Disabled
1 : oL5 @ Speed > L6-09 - Alarm
2 : oL5 @ |Speed| > L6-09 - Alarm
3 : oL5 @ Speed > L6-09 - Fault
4 : oL5 @ |Speed| > L6-09 - Fault
5 : UL5 @ Speed < L6-09 - Alarm
6 : UL5 @ |Speed| < L6-09 - Alarm
7 : UL5 @ Speed < L6-09 - Fault
8 : UL5 @ |Speed| < L6-09 - Fault
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed level where the drive will operate the mechanical deterioration detection
function, as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time for mechanical deterioration detection.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time that the drive will start mechanical deterioration detection triggered by the
cumulative operation time of the drive.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for forward motoring as a percentage, where motor rated
torque is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for reversed motoring as a percentage, where motor rated
torque is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for forward regenerative conditions as a percentage of the
motor rated torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for reversed regenerative conditions as a percentage of the
motor rated torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the integral time constant for the torque limit function.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
Ref.
(Range)
0
903
(0 - 8)
150%
904
(0 - 300%)
0.1 s
904
(0.0 - 10.0 s)
0 ms
904
(0 - 1000 ms)
0
904
(0 - 8)
110.0%
905
(-110.0 - 110.0%)
0.1 s
905
(0.0 - 10.0 s)
0 h
906
(0 - 65535 h)
Default
Ref.
(Range)
200%
907
(0 - 300%)
200%
907
(0 - 300%)
200%
907
(0 - 300%)
200%
907
(0 - 300%)
200 ms
908
(5 - 10000 ms)