5.3 UL Standards
Drive Model
2110
2138
2169
2211
2257
2313
2360
2415
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Table 5.18 Factory-Recommended Branch Circuit Protection: 200 V Class (HD)
Drive Model
2004
2006
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
2169
2211
2257
2313
2360
2415
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
256
Maximum Applicable Motor Output
kW (HP)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
-
Maximum Applicable Motor Output
kW (HP)
0.55 (0.5)
0.75 (1)
1.5 (2)
2.2 (3)
3 (4)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
Input Current Rating
A
Manufacturer: EATON/Bussmann
111
136
164
200
271
324
394
-
Input Current Rating
A
Manufacturer: EATON/Bussmann
3.6
4.8
8.9
12.7
17
20.7
30
40.3
58.2
78.4
96
82
111
136
164
200
271
324
394
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Semiconductor Protection Fuse
Rated Current
FWH-225A
*1
FWH-250A
FWH-275A
*1
FWH-300A
FWH-275A
*1
FWH-350A
FWH-325A
*1
FWH-450A
FWH-600A
FWH-800A
FWH-1000B
-
Semiconductor Protection Fuse
Rated Current
FWH-45B
FWH-45B
FWH-45B
FWH-50B
*1
FWH-80B
FWH-80B
*1
FWH-100B
FWH-80B
*1
FWH-100B
FWH-125B
FWH-150B
FWH-200B
FWH-225A
FWH-225A
*1
FWH-250A
FWH-225A
*1
FWH-250A
FWH-275A
*1
FWH-300A
FWH-275A
*1
FWH-350A
FWH-325A
*1
FWH-450A
FWH-600A
FWH-800A
FWH-1000B
FWH-1000B