12.10 n: Special Adjustment
Note:
If the drive detects dv3, dv4, or LSo, increase the setting value.
n8-94: Flux Position Estimation Method
No.
Name
(Hex.)
n8-94
Flux Position Estimation
Method
(012D)
Expert
0 : Softstarter
1 : Speed Feedback
Set n8-57 = 1 [HFI Overlap Selection = Enabled] to enable this parameter. Increases the stability when the speed
or load suddenly change, for example with rapid acceleration/deceleration or impact loads.
n8-95: Flux Position Est Filter Time
No.
Name
(Hex.)
n8-95
Flux Position Est Filter
Time
(012E)
Expert
Note:
Enabled when n8-94 = 1 [Flux Position Estimation Method = Speed Feedback].
940
V/f
CL-V/f
OLV
CLV
AOLV
Sets the criteria that the drive uses to find changes in speed or load. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant of the filter used for the recognition criteria value for speed and load
changes. Usually it is not necessary to change this setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
Determined by d5-01
(0, 1)
Default
(Range)
30 ms
(0 - 100 ms)