12.4 C: Tuning
When A1-02 = 3 or 7 [Control Method Selection = CLV or CLV/PM], the drive automatically sets C5-18 to the
load inertia ratio when you do Inertia Tuning or ASR Tuning.
C5-21: Motor 2 ASR Proportional Gain 1
No.
Name
(Hex.)
C5-21
Motor 2 ASR Proportional
Gain 1
(0356)
RUN
A higher gain provides a higher speed response. Usually, the gain increases with larger loads. Too much gain will
cause vibration.
Note:
• The drive usually sets Motor 2 ASR with C5-21 and C5-22 [Motor 2 ASR Integral Time 1]. You can also use C5-23 [Motor 2 ASR
Proportional Gain 2] instead of C5-21 when the speed is less than or equal to the frequency set in C5-27 [Motor 2 ASR Gain
Switchover Freq]. You can switch between C5-21 and C5-23 by setting H1-xx = 77 [MFDI Function Selection = ASR Gain (C5-03)
Select].
• The drive automatically adjusts C5-21 in ASR Tuning.
C5-22: Motor 2 ASR Integral Time 1
No.
Name
(Hex.)
C5-22
Motor 2 ASR Integral Time
1
(0357)
RUN
When you increase the integral time, the responsiveness will decrease. An integral time that is too short can cause
oscillation.
Note:
The drive usually sets Motor 2 ASR with C5-21 [Motor 2 ASR Proportional Gain 1] and C5-22. You can also use C5-24 [Motor 2 ASR
Integral Time 2] instead of C5-22 when the speed is less than or equal to the frequency set in C5-27 [Motor 2 ASR Gain Switchover
Freq].
C5-23: Motor 2 ASR Proportional Gain 2
No.
Name
(Hex.)
C5-23
Motor 2 ASR Proportional
Gain 2
(0358)
RUN
A higher gain provides a higher speed response. Usually, the gain increases with larger loads. Too much gain
causes vibration.
C5-24: Motor 2 ASR Integral Time 2
No.
Name
(Hex.)
C5-24
Motor 2 ASR Integral Time
2
(0359)
RUN
When you increase the integral time, the responsiveness will decrease. An integral time that is too short can cause
oscillation.
Note:
The drive usually sets Motor 2 ASR with C5-21 [Motor 2 ASR Proportional Gain 1] and C5-22 [Motor 2 ASR Integral Time 1]. You can
also use C5-24 [Motor 2 ASR Integral Time 2] instead of C5-22 when the speed is less than or equal to the frequency set in C5-27
[Motor 2 ASR Gain Switchover Freq].
C5-25: Motor 2 ASR Limit
No.
Name
(Hex.)
C5-25
Motor 2 ASR Limit
(035A)
710
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to adjust ASR response for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ASR integral time for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to adjust ASR response for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ASR integral time for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Set the motor 2 ASR output limit as a percentage of E1-04 [Maximum Output Frequency].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
Determined by E3-01
(0.00 - 300.00)
Default
(Range)
Determined by E3-01
(0.000 - 60.000 s)
Default
(Range)
Determined by E3-01
(0.00 - 300.00)
Default
(Range)
Determined by E3-01
(0.000 - 60.000 s)
Default
(Range)
5.0%
(0.0 - 20.0%)