YASKAWA GA700 Series Technical Manual page 999

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

Second Row: Log Data Information
This example shows the data text strings and data generated for the second row of log
data.
Example of generated data:
01,0012,160107111230,0101,0201,0102,0201,0103,0206,0107,0005,0108,0209,
0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,
000002
Nu mber of
No.
It e m
C h aracters
1
Attribute
2
File number
3
Time stamp
4
Monitor number
1
*1
*2
5
Monitor unit 1
6
Monitor number
2
7
Monitor Unit 2
:
:
22 Monitor number
10
23 Monitor Unit 10
24
Region Code
-
27
28 Row number
*1
If there is no data log monitor selected, the text string of [0000] is generated. [0000] is generated for
monitor number 5 and subsequent monitors for a short-term data log.
*2
Refer to
Table 12.88
Un i t Code
Un i t
( Hex.)
00
01
Hz
02
RPM
03
%
04
VAC
05
VDC
06
A
07
sec
Th ird and Subsequent Rows: Log Data
This example shows the data text strings and data generated for the third row of log data.
Example of generated data:
02,0012,160107111239,1770,1770,00BE,0118,0028,0000,0000,0000,0000,0000,
0000,0000,00000C
Nu mber of
No.
It e m
C h aracters
1
Attribute
2
2
File number
4
3
Time stamp
12
2
[01] shows that the record is a log data information record.
4
Long-term data log: Shows the [xxx] part (a 3-digit number) of the
Short-term data log: Shows the [xxx] part (a 3-digit number) of the
12
Date file was generated
4
Monitor number selected by
Ex.: 0101 (Dec.) for
4
Unit code and number of decimal places used for the monitor selected with
o5-03
U1-01
Example when
Number of decimal places = 2, Hz unit code = 01, monitor unit 1 = 0201 (Hex.)
4
Monitor number (Dec.) selected by
4
Unit code and number of decimal places used for the monitor selected with
o5-04
:
:
4
Monitor number (Dec.) selected by
4
Unit code and number of decimal places used for the monitor selected with
o5-12
4
-
6
Row number (Hex.) in the data log file
for information about unit codes.
Tab le 12.88 Unit Codes
Un i t Code
Un i t
( Hex.)
08
PPR
09
kW
0A
Ω
0B
ms
0C
kHz
0D
PSI
0E
MPM
0F
FPM
[02] shows that the record is a monitor data record for a long-term data log.
[03] shows that the record is a monitor data record for a short-term data log.
[04] shows that the record is a monitor data record for a trend log.
Long-term data log: Shows the [xxx] part (a 3-digit number) of the
Short-term data log: Shows the [xxx] part (a 3-digit number) of the
Data log data was retrieved (YYMMDDHHMMSS)
Trigger detection time for a short-term data log (common to all data)
De scription
[GLOG0xxx.csv] filename.
[SLOG0xxx.csv] filename + 1000.
o5-03 [Log Monitor Data 1]
U1-01
30.00 Hz:
=
o5-04 [Log Monitor Data 2]
o5-12 [Log Monitor Data10]
Un i t Code
Un i t
( Hex.)
10
11
12
us
13
min
14
15
16
kWH
17
MWH
De scription
[GLOG0xxx.csv] filename.
[SLOG0xxx.csv] filename + 1000.
Un i t Code
( Hex.)
H
18
V
19
1A
1B
1C
W
1D
1E
1F
D ocu ment No. E ZZ024048<1>
P r epared in October, 2021
Un i t
0H
15 / 19

Advertisement

Table of Contents
loading