YASKAWA GA700 Series Technical Manual page 677

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

b5-14: PID Feedback Loss Detection Time
No.
Name
(Hex.)
b5-14
PID Feedback Loss
Detection Time
(01B2)
b5-15: PID Sleep Function Start Level
No.
Name
(Hex.)
b5-15
PID Sleep Function Start
Level
(01B3)
The drive goes into Sleep mode when the PID output or frequency reference is less than b5-15 for longer than the
time set to b5-16 [PID Sleep Delay Time]. The drive continues operation when the PID output or frequency
reference is more than b5-15 for longer than the time set to b5-16.
b5-16: PID Sleep Delay Time
No.
Name
(Hex.)
b5-16
PID Sleep Delay Time
(01B4)
b5-17: PID Accel/Decel Time
No.
Name
(Hex.)
b5-17
PID Accel/Decel Time
(01B5)
RUN
The drive usually uses the acceleration and deceleration times set in C1-xx [Accel and Decel Times], but when
PID control is enabled, the drive applies C1-xx after PID output. If you frequently change the PID setpoint, the
drive responsiveness decreases. When resonance with PID control causes hunting, overshoot, or undershoot, set
b5-17 for longer acceleration and deceleration times.
Decrease C1-xx until hunting stops, then use b5-17 to check the acceleration and deceleration. To enable and
disable the setting in b5-17 through an MFDI terminal, set PID Soft Starter Disable [H1-xx = 34].
b5-18: b5-19 PID Setpoint Selection
No.
Name
(Hex.)
b5-18
b5-19 PID Setpoint
Selection
(01DC)
0 : Disabled
The drive does not use the value set in b5-19 as the PID setpoint.
1 : Enabled
The drive uses the value set in b5-19 as the PID setpoint.
b5-19: PID Setpoint Value
No.
Name
(Hex.)
b5-19
PID Setpoint Value
(01DD)
RUN
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that PID Feedback must be less than b5-13 [PID Feedback Loss Detection
Lvl] to detect PID Feedback Loss [FbL].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output level that triggers the PID Sleep function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a delay time to start or stop the PID Sleep function.
V/f
CL-V/f
OLV
CLV
AOLV
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive.
This is a soft-starter for the PID setpoint.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables b5-19 [PID Setpoint Value].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PID setpoint when b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.3 b: Application
Default
(Range)
1.0 s
(0.0 - 25.5 s)
Default
(Range)
Determined by A1-02
(0.0 - 590.0)
Default
(Range)
0.0 s
(0.0 - 25.5 s)
Default
(Range)
0.0 s
(0.0 - 6000.0 s)
Default
(Range)
0
(0, 1)
Default
(Range)
0.00%
(0.00 - 100.00%)
12
677

Advertisement

Table of Contents
loading

Table of Contents