d3: Jump Frequency

The Jump frequency is a function that sets the dead band to a specified frequency band. If a machine that operated
at constant speed is operated with variable speed, it can make resonance. To operate the machine without
resonance from the natural frequency of the machinery mechanical system, use a frequency band jump.
You can program the drive to have three different Jump frequencies. Sets d3-01[Jump Frequency 1] to d3-03
[Jump Frequency 3] to the center value for the frequency to avoid and sets d3-04 [Jump Frequency Width] to be
1/2 of the total band to avoid.
When you input a frequency reference that is the same as or near the Jump frequency width, the frequency
reference changes automatically.
The drive accelerates or decelerates the motor smoothly until the frequency reference is not in the range of the
Jump frequency band. The drive will use the active accel/decel time to go through the specified dead band range.
If the frequency reference is not in the range of the Jump frequency band, switch to constant speed operation.
Note:
• When you set Jump Frequencies 1 to 3, make sure that the parameters do not overlap. The drive will not indicate this condition.
• When the drive is in the range of the Jump frequency, the frequency reference changes automatically. When the drive jumps
frequencies, the output frequency changes smoothly as specified by the values set in C1-01 [Acceleration Time 1] and C1-02
[Deceleration Time 1].
d3-01: Jump Frequency 1
No.
Name
(Hex.)
d3-01
Jump Frequency 1
(0294)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
d3-02: Jump Frequency 2
No.
Name
(Hex.)
d3-02
Jump Frequency 2
(0295)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
724
Figure 12.64 Jump Frequency
V/f
CL-V/f
OLV
CLV
AOLV
Sets the median value of the frequency band that the drive will avoid.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the median value of the frequency band that the drive will avoid.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
0.0 Hz
(Determined by A1-02)
Default
(Range)
0.0 Hz
(Determined by A1-02)