Setting Value
Function
42
Run Command (2-Wire
Sequence 2)
43
FWD/REV (2-Wire
Sequence 2)
44
Add Offset Frequency 1
(d7-01)
45
Add Offset Frequency 2
(d7-02)
46
Add Offset Frequency 3
(d7-03)
47
Node Setup (CANopen)
60
DC Injection Braking
Command
61
Speed Search from Fmax
62
Speed Search from Fref
63
Field Weakening
65
KEB Ride-Thru 1
Activate (N.C.)
66
KEB Ride-Thru 1
Activate (N.O.)
67
Communications Test
Mode
68
High Slip Braking
(HSB) Activate
6A
Drive Enable
71
Torque Control
72
Zero Servo
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Run command for 2-wire sequence 2. Set this function and H1-xx = 43 [FWD/REV (2-Wire Sequence 2)]
together.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward RUN (2-Wire), Reverse RUN (2-
Wire)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and H1-xx = 42 [Run Command (2-
Wire Sequence 2)] together.
ON : Reverse Run
OFF : Forward Run
Note:
• You must input the Run command to rotate the motor.
• This function will not operate at the same time as H1-xx = 40, 41 [Forward RUN (2-Wire), Reverse RUN (2-
Wire)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to add the offset frequency set in d7-01 [Offset Frequency 1] to the frequency reference when the
terminal activates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to add the offset frequency set in d7-02 [Offset Frequency 2] to the frequency reference when the
terminal activates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to add the offset frequency set in d7-03 [Offset Frequency 3] to the frequency reference when the
terminal activates.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from
the host controller.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use DC Injection Braking to stop the motor.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available with a PM motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at
Start = Disabled] to not allow speed search at start.
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 [Speed Search from Fmax]
and H1-xx = 62 [Speed Search from Fref] are set at the same time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at
Start = Disabled] to not allow speed search at start.
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 [Speed Search from Fmax]
and H1-xx = 62 [Speed Search from Fref] are set at the same time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01
[Field Weakening Level] and d6-02 [Field Weakening Frequency Limit] when the input terminal is activated.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
V/f
CL-V/f
OLV
CLV
AOLV
Set the function for the drive to self-test RS-485 serial communications operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use high-slip braking to stop the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to show dnE [Drive Disabled] on the keypad and ignore Run commands when the terminal is
OFF.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to switch between torque control and speed control.
ON : Torque control
OFF : Speed control
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to hold a stopped motor.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.10 H: Terminal Functions
Ref.
814
815
815
815
815
815
815
816
816
816
816
817
817
817
817
817
818
11
525