YASKAWA GA700 Series Technical Manual page 664

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

12.3 b: Application
b3-25: Speed Search Wait Time
No.
Name
(Hex.)
b3-25
Speed Search Wait Time
(01C8)
Expert
If the drive detects these faults during speed search, increase the setting value:
• oC [Overcurrent]
• ov [Overvoltage]
• SEr [Speed Search Retries Exceeded]
b3-26: Direction Determination Level
No.
Name
(Hex.)
b3-26
Direction Determination
Level
(01C7)
Expert
b3-27: Speed Search RUN/BB Priority
No.
Name
(Hex.)
b3-27
Speed Search RUN/BB
Priority
(01C9)
Expert
Executes Speed Search from Fmax or Fref [H1-xx = 61/62] for initial speed searches or from the MFDI terminal.
0 : SS Only if RUN Applied Before BB
1 : SS Regardless of RUN/BB Sequence
b3-29: Speed Search Back-EMF Threshold
No.
Name
(Hex.)
b3-29
Speed Search Back-EMF
Threshold
(077C)
Expert
To make adjustments, gradually decrease the setting value. If you decrease the setting value too much, speed
search will not operate correctly.
b3-31: Spd Search Current Reference Lvl
No.
Name
(Hex.)
b3-31
Spd Search Current
Reference Lvl
(0BC0)
Expert
Set this parameter as a ratio of E2-03 [Motor No-Load Current]. The setting is a ratio with respect to 30% of the
motor rated current when E2-03 ≤ E2-01 [Motor Rated Current (FLA)] × 0.3.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], the setting is a ratio with respect to E9-06 [Motor Rated Current (FLA)] × 0.5.
b3-32: Spd Search Current Complete Lvl
No.
Name
(Hex.)
b3-32
Spd Search Current
Complete Lvl
(0BC1)
Expert
664
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time the drive will wait to start the Speed Search Retry function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to find the motor rotation direction. Increase the value if the drive cannot find the
direction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the conditions necessary to start Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the induced voltage for motors that use Speed Search. The drive will start Speed Search
when the motor induced voltage level is the same as the setting value. Usually it is not necessary
to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level that decreases the output current during Current Detection Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level that completes Speed Search.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
0.5 s
(0.0 - 30.0 s)
Default
(Range)
1000
(40 to 60000)
Default
(Range)
0
(0, 1)
Default
(Range)
10%
(0 - 10%)
Default
(Range)
1.50
(1.50 - 3.50)
Default
(Range)
1.20
(0.00 - 1.49)