F5: Digital Output Option - YASKAWA GA700 Series Technical Manual

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

12.7 F: Options
F4-04: Terminal V2 Gain
No.
Name
(Hex.)
F4-04
Terminal V2 Gain
(0394)
RUN
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Terminal V2 Signal Level] to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V2 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V2
outputs a maximum voltage of 10 V.
• F4-03 [Terminal V2 Function Selection] = 103 (U1-03: Output Current)
• F4-04 = 50.0%
• F4-06 [Terminal V2 Bias] = 0.0%
• F4-08 = 0 (0 V to 10 V)
F4-05: Terminal V1 Bias
No.
Name
(Hex.)
F4-05
Terminal V1 Bias
(0395)
RUN
The maximum output voltage output from terminal V1 is ±10 V. Use F4-07 [Terminal V1 Signal Level] to set the
signal level.
F4-06: Terminal V2 Bias
No.
Name
(Hex.)
F4-06
Terminal V2 Bias
(0396)
RUN
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Terminal V2 Signal Level] to set the
signal level.
F4-07: Terminal V1 Signal Level
No.
Name
(Hex.)
F4-07
Terminal V1 Signal Level
(0397)
0 : 0 to 10 V
1 : -10 to 10 V
F4-08: Terminal V2 Signal Level
No.
Name
(Hex.)
F4-08
Terminal V2 Signal Level
(0398)
0 : 0 to 10 V
1 : -10 to 10 V

F5: Digital Output Option

F5 parameters set the output mode and function of output signals when you use digital output option card DO-A3.
774
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal output
level from terminal V2 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V1. When an output for monitoring
items is 0%, this parameter sets the analog signal output level from the V1 terminal as a
percentage of 10 V or 20 mA.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog signal
sent from the V2 terminal at 10 V or 20 mA as 100% when an output for monitoring items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output signal level for terminal V1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output signal level for terminal V2.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
50.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)

Advertisement

Table of Contents
loading

Table of Contents