12.8 H: Terminal Functions
4B: During Short Circuit Braking
Setting Value
Function
4B
During Short Circuit
Braking
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
• Refer to
b2: DC Injection Braking and Short Circuit Braking on page 654
4C: During Fast Stop
Setting Value
Function
4C
During Fast Stop
4D: oH Pre-Alarm Time Limit
Setting Value
Function
4D
oH Pre-Alarm Time Limit
Note:
Refer to "L8-03: Overheat Pre-Alarm Ope Selection" for more information about drive derating operation.
4E: Braking Transistor Fault (rr)
Setting Value
Function
4E
Braking Transistor Fault
(rr)
4F: Braking Resistor Overheat (rH)
Setting Value
Function
4F
Braking Resistor Overheat
(rH)
The braking resistor overheats when the deceleration time is short and there is too much motor regeneration
energy.
60: Internal Cooling Fan Failure
Setting Value
Function
60
Internal Cooling Fan
Failure
61: Pole Position Detection Complete
Setting Value
Function
61
Pole Position Detection
Complete
62: Modbus Reg 1 Status Satisfied
Setting Value
Function
62
Modbus Reg 1 Status
Satisfied
63: Modbus Reg 2 Status Satisfied
Setting Value
Function
63
Modbus Reg 2 Status
Satisfied
842
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates during Short Circuit Braking.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the fast stop is in operation.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and oH [Heatsink
Overheat] does not clear after the drive decreases the frequency for 10 cycles.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking Transistor
Fault] fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat] fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a cooling fan failure in the drive.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position of the PM
motor.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register address set
with H2-07 [Modbus Register 1 Address Select] activates.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register address set
with H2-09 [Modbus Register 2 Address Select] activates.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
for more information.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM