12.8 H: Terminal Functions
Note:
• The ON/OFF operation of terminal Sx set in Analog Terminal Input Selection [H1-xx = C] has an effect on only the analog input
terminal selected with H3-14.
• When H1-xx ≠ C, the functions set to terminals A1 to A3 are always enabled.
H3-16: Terminal A1 Offset
No.
Name
(Hex.)
H3-16
Terminal A1 Offset
(02F0)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal
of 0 V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-01= 2] or 0 mA
[H3-01 = 3] is input.
H3-17: Terminal A2 Offset
No.
Name
(Hex.)
H3-17
Terminal A2 Offset
(02F1)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal
of 0 V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-09 = 2] or 0 mA
[H3-09 = 3] is input.
H3-18: Terminal A3 Offset
No.
Name
(Hex.)
H3-18
Terminal A3 Offset
(02F2)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal
of 0 V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-05 = 2] or 0 mA
[H3-05 = 3] is input.
H3-40: Mbus Reg 15C1h Input Function
No.
Name
(Hex.)
H3-40
Mbus Reg 15C1h Input
Function
(0B5C)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the
function. Sets the function for MEMOBUS/Modbus register 15C1h.
Refer to
Multi-Function Analog Input Terminal Settings on page 851
H3-41: Mbus Reg 15C2h Input Function
No.
Name
(Hex.)
H3-41
Mbus Reg 15C2h Input
Function
(0B5F)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the
function. Sets the function for MEMOBUS/Modbus register 15C2h.
Refer to
Multi-Function Analog Input Terminal Settings on page 851
850
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A3. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MEMOBUS AI1 function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MEMOBUS AI2 function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
for the setting values.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
for the setting values.
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
0
(-500 - +500)
Default
(Range)
0
(-500 - +500)
Default
(Range)
0
(-500 - +500)
Default
(Range)
F
(4 - 2F)
Default
(Range)
F
(4 - 2F)