8.5 Replace the Drive
2.
Loosen the main circuit terminal block screws to fully open the terminal block opening.
Note:
The terminal block openings ship from the factory as fully open.
3.
Put wires with prepared ends into the main circuit terminal block.
Note:
If there is a jumper between terminals +1 and +2, loosen the terminal block screws to remove the jumper before you wire to
terminals +1 and +2.
4.
Tighten the screws to the specified torque.
5.
Check the terminal sign that you wired and use a nipper as shown in
cutaway section of the wiring cover.
A - Cutaway sections
Note:
• Different drive models have different wiring cover shapes.
• Only clip the section of the wiring cover that applies to the wired terminal. If you clip areas that do not apply to wired
terminals, the protective enclosure will not keep its IP20 protective level.
• Be careful when clipping the cutaway section of the wiring cover, as the section may fly out in unpredictable directions.
• Make sure that the clipped section does not cause damage to the wires.
• If you use wires that are not specified by Yaskawa, the protective enclosure could lose its IP20 protective level, although the
wiring cover is correct. Contact Yaskawa or your nearest sales representative for more information.
416
Figure 8.73 Loosen Terminal Block Screws
Figure 8.74 Install the Electrical Wire
Figure 8.75 Tighten Terminal Block Screws
Figure 8.76 Clip the Cutaway Section of the Wiring Cover
Figure 8.76
B - Clip here with nippers
YASKAWA SIEPC71061705H GA700 Series Technical Manual