Note:
When b5-90 [EZ Sleep Unit] changes, this parameter does not automatically update. Set this parameter again after you change b5-90.
b5-93: EZ Sleep Time
No.
Name
(Hex.)
b5-93
EZ Sleep Time
(0B93)
RUN
b5-94: EZ Sleep Wake-up Level
No.
Name
(Hex.)
b5-94
EZ Sleep Wake-up Level
(0B94)
RUN
Note:
The values of b5-20 [PID Unit Selection], b5-38 [PID User Unit Display Scaling], and b5-39 [PID User Unit Display Digits] set the
units. When b5-20, b5-38, and b5-39 change, this parameter does not automatically update. Set this parameter again after you change
b5-20, b5-38, and b5-39 are changed.
• When b5-95 = 0 [EZ Sleep Wake-up Mode = Absolute]:
When b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)], and the PID Feedback [H3-xx
= B] is less than the value of b5-94 for a time longer than the value of b5-96 [EZ Sleep Wake-up Time], the
drive will exit sleep and start operation again. When b5-09 = 1 [Reverse Output (Reverse Acting)], and the PID
feedback is more than setting value of b5-94 for a time longer than the setting value of b5-96, the drive will exit
sleep and start operation again.
• When b5-95 = 1 [Setpoint Delta]:
When b5-09 = 0, and the PID feedback is less than the value of "PID setpoint value - b5-94" for a time longer
than the value of b5-96, the drive will exit sleep and start operation again. When b5-09 = 1, and the PID
feedback is more than the value of "PID setpoint value + b5-94" for a time longer than the setting value of b5-
96, the drive will exit sleep and start operation again.
b5-95: EZ Sleep Wake-up Mode
No.
Name
(Hex.)
b5-95
EZ Sleep Wake-up Mode
(0B95)
0 : Absolute
1 : Setpoint Delta
b5-96: EZ Sleep Wake-up Time
No.
Name
(Hex.)
b5-96
EZ Sleep Wake-up Time
(0B96)
RUN
When the PID feedback is less than the value of b5-94 [EZ Sleep Wake-up Level] continuously for the time set in
b5-96, the drive will exit sleep and start operation again.

b6: Dwell Function

The Dwell function momentarily holds the output frequency at start and stop.
This prevents motor speed loss when you start and stop heavy loads. The Dwell function is also enabled when
backlash on the machine side causes sudden movement at the start of acceleration and deceleration.
At the start of acceleration, the drive uses the output frequency and acceleration time set for the Dwell function to
automatically operate at low speed to minimize the effects of backlash. Then, the drive can accelerate again. The
Dwell function operates the same for deceleration.
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the output frequency or motor speed must be less than b5-92 [EZ
Sleep Level] to enter Sleep Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level at which the drive resumes operation when exiting Sleep Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the wake-up mode to use when exiting Sleep Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the EZ Wake-up time.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.3 b: Application
Default
(Range)
5.0 s
(0.0 - 1000.0 s)
Default
(Range)
0.00%
(0.00 - 600.00%)
Default
(Range)
0
(0, 1)
Default
(Range)
1.0 s
(0.0 - 1000.0 s)
12
683