12.3 b: Application
Note:
Refer to this table for Drive Mode and Programming Mode functions.
Mode
Drive Mode
Monitors
Parameters
User Custom Parameters
Parameter Backup/Restore
Programming Mode
Modified Parameters/Fault Log
Auto-Tuning
Initial Setup Screen
Diagnostic Tools
0 : Disregard RUN while Programming
The drive does not accept the Run command when setting the parameters in the Programming Mode.
1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source when setting the parameters in Programming
Mode.
2 : Allow Programming Only at Stop
The drive does not allow the user to enter the Programming Mode while the drive is operating. The keypad does
not display the Programming Mode while the drive is operating.
b1-14: Phase Order Selection
No.
Name
(Hex.)
b1-14
Phase Order Selection
(01C3)
0 : Standard
1 : Switch Phase Order
b1-15: Frequency Reference Selection 2
No.
Name
(Hex.)
b1-15
Frequency Reference
Selection 2
(01C4)
This parameter is enabled when H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is
activated.
Note:
• Push
on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
• If the frequency reference is 0 Hz or ≤ E1-09 [Minimum Output Frequency] and the drive receives a Run command, the
keypad will flash. Check the setting for the frequency reference input and enter a value more than or equal to E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input signal.
• Voltage Input
Refer to
Table 12.24
to use a voltage signal input to one of the MFAI terminals.
650
Keypad Screen
Sets monitor display.
Changes parameter settings.
Shows the User Parameters.
Saves parameters to the keypad as backup.
Shows modified parameters and fault history.
Auto-Tunes the drive.
Changes initial settings.
Sets data logs and backlight.
V/f
CL-V/f
OLV
CLV
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
V/f
CL-V/f
OLV
CLV
Sets the input method for frequency reference 2.
Function
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 4)
on the

Advertisement

Table of Contents
loading

Table of Contents