Installing the External EMC Noise Filter
Drive models 2xxxA and 4xxxA must meet conditions in this section to comply with EN 61800-3:2004+A1:2012.
Connect an EMC noise filter that complies with European standards as specified by Yaskawa to the input side
(primary side). Refer to
External EMC Noise Filter Selection on page 239
Use this procedure to install an EMC noise filter to make equipment and devices added to the drive comply with
the EMC Directive.
1.
Install the drive and EMC noise filter on the same grounded metal plate.
2.
Wire the drive and motor.
3.
Ground the wire shielding on the drive side and motor side.
A - Drive
B - 10 m (32.8 ft) maximum
C - Motor
Note:
• Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
• The maximum wiring length between the drive and motor is 10 m (32.8 ft). Keep the wire as short as possible.
• Keep the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
A - Braided shield cable
B - Metal plate
YASKAWA SIEPC71061705H GA700 Series Technical Manual
D - Metal conduit
E - Grounding wire
Figure 5.15 Wiring the Drive and Motor
C - Cable clamp (conductive)
Figure 5.16 Ground the Shield
5.2 European Standards
to select the correct EMC noise filter.
5
237