11.11 L: Protection Functions
No.
Name
(Hex.)
L4-03
Speed Agree Detection
Level (+/-)
(049B)
L4-04
Speed Agree Detection
Width (+/-)
(049C)
L4-05
Fref Loss Detection
Selection
(049D)
L4-06
Frequency Reference
@Loss of Ref
(04C2)
L4-07
Speed Agree Detection
Selection
(0470)

L5: Fault Restart

No.
Name
(Hex.)
L5-01
Number of Auto-Restart
Attempts
(049E)
L5-02
Fault Contact at Restart
Select
(049F)
L5-03
Continuous Method Max
Restart T
(04A0)
L5-04
Interval Method Restart
Time
(046C)
L5-05
Auto-Restart Method
(0467)
552
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to detect speed agree or motor speed.
Sets the speed agree detection level or motor speed detection level when H2-01 to H2-
03 = 13, 14, 15, 16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree
2, Frequency Detection 3, Frequency Detection 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width to detect speed agree or motor speed.
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = 13, 14, 15,
16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency
Detection 3, Frequency Detection 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the operation when the drive detects a loss of frequency reference.
0 : Stop
1 : Run at (L4-06 x Last Reference)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference as a percentage to continue drive operation after it detects a
frequency reference loss. The value is a percentage of the frequency reference before
the drive detected the loss.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the condition that activates speed detection.
0 : No Detection during Baseblock
1 : Detection Always Enabled
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times that the drive will try to restart.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = E]
while the drive is automatically restarting.
0 : Active Only when Not Restarting
1 : Always Active
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time for which the drive will try to restart. If the drive cannot restart inthe time
set in L5-03, the drive detects a fault. This is available when L5-05 = 0 [Auto-Restart
Method = Continuous/Immediate Attempts].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time interval between each Auto Restart attempt. This function is enabled when
L5-05 = 1 [Auto Restart Operation Selection = Use L5-04 Time].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the count method for the Auto Restart operation.
0 : Continuous/Immediate Attempts
1 : Interval/Attempt after L5-04 sec
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
Ref.
(Range)
Determined by A1-02
896
(Determined by A1-02)
Determined by A1-02
897
(Determined by A1-02)
0
897
(0, 1)
80.0%
897
(0.0 - 100.0%)
0
897
(0, 1)
Default
Ref.
(Range)
0
898
(0 - 10 times)
0
898
(0, 1)
10.0 s
898
(0.5 - 180.0 s)
10.0 s
899
(0.5 - 600.0 s)
0
899
(0, 1)