12.7 F: Options
1 : AB Pulse Detection
F1-30: Motor 2 Encoder PCB Port Select
No.
Name
(Hex.)
F1-30
Motor 2 Encoder PCB Port
Select
(03AA)
0 : CN5-C
One option card receives the speed feedback signals from motor 1 and motor 2.
1 : CN5-B
Two option cards receive the speed feedback signals from motor 1 and motor 2.
F1-31: Encoder 2 Pulse Count (PPR)
No.
Name
(Hex.)
F1-31
Encoder 2 Pulse Count
(PPR)
(03B0)
F1-32: Encoder 2 Rotation Selection
No.
Name
(Hex.)
F1-32
Encoder 2 Rotation
Selection
(03B1)
Refer to the option card installation manual for more information about how to set the encoder pulse output
sequence and make sure that it is correct.
0 : Pulse A leads in FWD Direction
1 : Pulse B leads in FWD Direction
F1-33: Encoder 2 Gear Teeth 1
No.
Name
(Hex.)
F1-33
Encoder 2 Gear Teeth 1
(03B2)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-33 = 0 or F1-34 = 0, the gear ratio is 1.
F1-34: Encoder 2 Gear Teeth 2
No.
Name
(Hex.)
F1-34
Encoder 2 Gear Teeth 2
(03B3)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-33 = 0 or F1-34 = 0, the gear ratio is 1.
764
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive port to install the motor 2 encoder option card.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of output pulses for each motor revolution for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output sequence for the A and B pulses from the encoder for motor 2. This parameter
assumes that the motor is operating in the forward direction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the motor side for motor 2. This parameter and F1-34 [Encoder
2 Gear Teeth 2] set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the load side for motor 2. This parameter and F1-33 [Encoder 2
Gear Teeth 1] set the gear ratio between the motor and encoder.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
1
(0, 1)
Default
(Range)
1024 ppr
(1 - 60000 ppr)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 1000)
Default
(Range)
0
(0 - 1000)