12.3 b: Application
b5-65: PID Differential FB Monitor Bias
No.
Name
(Hex.)
b5-65
PID Differential FB
Monitor Bias
(119F)
b5-66: PID Feedback Monitor Level
No.
Name
(Hex.)
b5-66
PID Feedback Monitor
Level
(11DE)
0 : Absolute
1 : Bi-directional (+/-)
b5-67: PID Differential FB Monitor Lvl
No.
Name
(Hex.)
b5-67
PID Differential FB
Monitor Lvl
(11DF)
0 : Absolute
1 : Bi-directional (+/-)
b5-89: Sleep Method Selection
No.
Name
(Hex.)
b5-89
Sleep Method Selection
(0B89)
RUN
0 : Standard
1 : EZ Sleep/Wake-up
b5-90: EZ Sleep Unit
No.
Name
(Hex.)
b5-90
EZ Sleep Unit
(0B90)
0 : 0.1Hz units
1 : rev/min
b5-91: EZ Sleep Minimum Speed
No.
Name
(Hex.)
b5-91
EZ Sleep Minimum Speed
(0B91)
RUN
Note:
The value of b5-90 [EZ Sleep Unit] sets the units. When b5-90 changes, this parameter does not automatically update. Set this parameter
again after you change b5-90 is changed.
b5-92: EZ Sleep Level
No.
Name
(Hex.)
b5-92
EZ Sleep Level
(0B92)
RUN
682
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level for the monitor specified in b5-55 [PID Feedback Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets sleep and wake up operation when using PID.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ Sleep Level].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the largest value
from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [Frequency Reference Lower
Limit].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value that the output frequency or motor speed must be less than for longer than b5-93
[EZ Sleep Time] to enter Sleep Mode.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
0.00
(-10.00 - +10.00)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Default
(Range)
-1
0.0 Hz or 0 min
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))