7.4 Fault
Code
Name
oL2
Drive Overload
Note:
• The drive detects this fault if the electronic thermal protector of the drive started the drive overload protection.
• Do a Fault Reset to clear the fault.
• L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
Code
Name
oL3
Overtorque Detection 1
Note:
• The drive detects this fault if the drive output current is more than the level set in L6-02 for longer than L6-03.
• Do a Fault Reset to clear the fault.
• If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in L6-01 [Torque Detection Selection 1].
• L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
Code
Name
oL4
Overtorque Detection 2
Note:
• The drive detects this fault if the drive output current is more than the level set in L6-05 for longer than L6-06.
• Do a Fault Reset to clear the fault.
• If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in L6-04 [Torque Detection Selection 2].
• L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
Code
Name
oL5
Mechanical Weakening Detection 1
Note:
• Do a Fault Reset to clear the fault.
• If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in L6-08.
342
Causes
The load is too large.
The acceleration/deceleration times or cycle times
are too short.
The V/f pattern does not fit the motor qualities.
The drive capacity is too small.
Overload occurred while running at low speed.
The torque compensation gain is too large.
The speed search-related parameters are set
incorrectly.
Phase loss in the input power supply is causing the
output current to change.
Overload occurred during overexcitation
deceleration.
Causes
A fault occurred on the machine.
Example: The machine is locked.
The parameters are incorrect for the load.
Causes
A fault occurred on the machine.
Example: The machine is locked.
The parameters are incorrect for the load.
Causes
The drive detected overtorque as specified by the
conditions for mechanical weakening detection set
in L6-08 [Mechanical Fatigue Detect Select].
Possible Solutions
Decrease the load.
• Examine the acceleration/deceleration times and the motor
start/stop frequencies (cycle times).
• Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
• Examine the ratios between the V/f pattern frequency and
voltage. Decrease the voltage if it is too high compared to the
frequency.
• Adjust E1-04 to E1-10 [V/f Pattern Parameters]. Decrease the
values set in E1-08 [Mid Point A Voltage] and E1-10
[Minimum Output Voltage]. For motor 2, adjust E3-04 to E3-
10.
Note:
If the values set in E1-08 and E1-10 are too low, the overload
tolerance will decrease at low speeds.
Replace the drive with a larger capacity model.
• Decrease the load when running at low speed.
• Replace the drive with a larger capacity model.
• Decrease the value set in C6-02 [Carrier Frequency
Selection].
Decrease the value set in C4-01 [Torque Compensation Gain] to
make sure that the motor does not stall.
• Examine the settings for all speed search-related parameters.
• Adjust b3-03 [Speed Search Deceleration Time].
• Set b3-24 = 1 [Speed Search Method Selection = Speed
Estimation] after Auto-Tuning.
• Correct errors with the wiring for main circuit drive input
power.
• Make sure that there is no phase loss, and repair problems.
• Decrease the value set in n3-13 [OverexcitationBraking (OEB)
Gain].
• Decrease the value set in n3-21 [HSB Current Suppression
Level].
Possible Solutions
Examine the machine and remove the cause of the fault.
Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque
Detection Time 1] settings.
Possible Solutions
Examine the machine and remove the cause of the fault.
Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque
Detection Time 2] settings.
Possible Solutions
Do a deterioration diagnostic test on the machine side.
YASKAWA SIEPC71061705H GA700 Series Technical Manual