11.5 b: Application
No.
Name
(Hex.)
b5-56
PID Feedback Monitor
Gain
(0BE2)
b5-57
PID Feedback Monitor
Bias
(11DD)
b5-58
PID Setpoints 2
(1182)
RUN
b5-59
PID Setpoints 3
(1183)
RUN
b5-60
PID Setpoints 4
(1184)
RUN
b5-61
PID Trim Mode Lower
Limit Sel
(119A)
b5-62
PID Trim Mode Lower
Limit Value
(119B)
b5-63
PID Differential FB
Monitor Sel
(119C)
b5-64
PID Differential FB
Monitor Gain
(119D)
b5-65
PID Differential FB
Monitor Bias
(119F)
b5-66
PID Feedback Monitor
Level
(11DE)
b5-67
PID Differential FB
Monitor Lvl
(11DF)
b5-89
Sleep Method Selection
(0B89)
RUN
b5-90
EZ Sleep Unit
(0B90)
b5-91
EZ Sleep Minimum
Speed
(0B91)
RUN
488
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for the monitor set in b5-55 [PID Feedback Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias for the monitor specified in b5-55 [PID Feedback Monitor Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Select = PID Setpoint
Selection 1/2]. This value is a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Select = PID Setpoint
Selection 1/2]. This value is a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Select = PID Setpoint
Selection 1/2]. This value is a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that adjusts the PID output in relation to the frequency reference.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PID Trim Mode Lower Limit Value as a percentage of the maximum output
frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Selects the monitor (Ux-xx) used as the PID Differential Feedback. Set the x-xx part of
the Ux-xx [Monitor].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level for the monitor specified in b5-55 [PID Feedback Monitor
Selection].
0 : Absolute
1 : Bi-directional (+/-)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor
Sel].
0 : Absolute
1 : Bi-directional (+/-)
V/f
CL-V/f
OLV
CLV
AOLV
Sets sleep and wake up operation when using PID.
0 : Standard
1 : EZ Sleep/Wake-up
V/f
CL-V/f
OLV
CLV
AOLV
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ Sleep
Level].
0 : 0.1Hz units
1 : rev/min
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the
largest value from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [Frequency
Reference Lower Limit].
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
Ref.
(Range)
1.00
680
(0.00 - 10.00)
0.00
680
(-10.00 - +10.00)
0.00%
680
(0.00 - 100.00%)
0.00%
680
(0.00 - 100.00%)
0.00%
680
(0.00 - 100.00%)
0
681
(0, 1)
0.00%
681
(0.00 - 100.00%)
000
681
(000 - 999)
1.00
681
(0.00 - 10.00)
0.00
682
(-10.00 - +10.00)
0
682
(0, 1)
0
682
(0, 1)
0
682
(0, 1)
0
682
(0, 1)
0.0 Hz or 0 min
-1
(r/min)
682
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))