b2: DC Injection Braking and Short Circuit Braking

b2 parameters set the DC Injection Braking and Short Circuit Braking functions.
• DC Injection Braking: A braking method that injects DC current into the motor windings. This function should
not be used too frequently, because it generates a fair amount of heat in the motor.
• Short Circuit Braking: A braking method for PM motors.
b2-01: DC Injection/Zero SpeedThreshold
No.
Name
(Hex.)
b2-01
DC Injection/Zero
SpeedThreshold
(0189)
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to Stop].
When the control method selected in A1-02 [Control Method Selection] changes, the b2-01 function changes.
Parameter Settings
A1-02 = 0, 1, 2 [V/f, CL-V/f, OLV]
A1-02 = 4 [AOLV] and n4-72 = 0 [Speed Feedback
Mode = With Encoder]
A1-02 = 5, 6, 8 [OLV/PM, AOLV/PM, EZOLV]
654
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency to start DC Injection Braking, Short Circuit Braking, or Zero Servo near the
end of a stop ramp.
Parameter b2-01 sets the frequency to start DC Injection Braking at stop. When the output frequency is less than or
equal to the value set in b2-01, the drive will inject the quantity of DC current set in b2-02 [DC Injection Braking
Current] into the motor for the time set in b2-04 [DC Inject Braking Time at Stop].
Figure 12.25 DC Injection Braking at Stop
Note:
When b2-01 ≤ E1-09 [Minimum Output Frequency], the drive will start DC Injection Braking from the frequency
set in E1-09.
Parameter b2-01 sets the frequency to start Short Circuit Braking at stop. When the output frequency is less than or
equal to the value set in b2-01, the drive will do Short Circuit Braking for the time set in b2-13 [Short Circuit Brake
Time @ Stop]. When b2-04 > 0.00 s, the drive will complete Short Circuit Braking, then do DC Injection Braking for
the time set in b2-04.
Figure 12.26 Short Circuit Braking at Stop
Note:
When b2-01 ≤ E1-09, the drive will start Short Circuit Braking from the frequency set in E1-09. If b2-01 and E1-
09 = 0 Hz, the drive will not do Short Circuit Braking.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Functions of b2-01
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
Determined by A1-02
(0.0 - 10.0 Hz)