1: Zero Speed
Setting Value
Function
1
Zero Speed
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting
0
V/f Control
1
V/f Control with Encoder
2
Open Loop Vector
3
Closed Loop Vector
4
Advanced OpenLoop Vector Control
5
PM Open Loop Vector
6
PM Advanced Open Loop Vector
7
PM Closed Loop Vector Control
8
EZ Open Loop Vector Control
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency ≥ value of E1-09 or b2-01.
2: Speed Agree 1
Setting Value
Function
2
Speed Agree 1
Note:
• The detection function operates in the two motor rotation directions.
• The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4
and n4-72 = 1.
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is
running.
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero
SpeedThreshold].
Control method selection
Figure 12.93 Zero Speed Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection
Width].
Figure 12.94 Speed Agree 1 Time Chart
12.8 H: Terminal Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Parameter Used as the Reference
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
E1-09
E1-09
b2-01
E1-09
E1-09
E1-09
E1-09
b2-01
E1-09
831
12