F2: Analog Input Option - YASKAWA GA700 Series Technical Manual

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

12.7 F: Options
0 : EnDat Sin/Cos
1 : EnDat Serial Only
2 : HIPERFACE
F1-51: PG-F3 PGoH Detection Level
No.
Name
(Hex.)
F1-51
PG-F3 PGoH Detection
Level
(03D3)
The drive will detect PGoH if the value of this parameter is smaller than the value of
Regarding the expression
is the single-track (phase A) output from the encoder.
Note:
This function is enabled when F1-20 = 1 [Encoder 1 PCB Disconnect Detect = Enabled].
F1-52: Serial Encoder Comm Speed
No.
Name
(Hex.)
F1-52
Serial Encoder Comm
Speed
(03D4)
Note:
This function is enabled when F1-50 = 1 or 2 [PG-F3 Option Encoder Type = EnDat Serial Only or HIPERFACE].
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps

F2: Analog Input Option

F2 parameters set the operation of the drive when you use analog input option card AI-A3. The AI-A3 card has 3
input terminals that accept voltages of -10 V to +10 V (20 kΩ) or currents of 4 mA to 20 mA (250 Ω). Install the
AI-A3 card to enable setting very accurate analog references with high resolution.
Refer to the AI-A3 option manual for more information about how to install, wire, and set the AI-A3 card.
WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are
correct. If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
F2-01: Analog Input Function Selection
No.
Name
(Hex.)
F2-01
Analog Input Function
Selection
(038F)
Note:
When the AI-A3 card is not mounted in the drive, analog input terminals A1 to A3 on the drive are always enabled. The setting of this
parameter does not have an effect.
0 : 3 Independent Channels
Set F2-01 = 0 to increase the precision of A/D conversion when you use the functions for terminals A1 to A3 on
the drive as they are. You can input the MFAI signal from terminals V1 through V3 for AI-A3. The functions for
terminals A1, A2, and A3 on the drive are sent to terminals V1, V2, and V3 for AI-A3. Use gain and bias
adjustment when you input current to set signals to have negative numbers.
Note:
• Set b1-01 = 1 [Frequency Reference Selection 1 = Analog Input] to set inputs individually.
• If F2-01 = 0 and b1-01 = 3 [Option PCB], the drive will detect oPE05 [Run Cmd/Freq Ref Source Sel Err].
Figure 12.77
shows the individual input of analog inputs. H3-xx parameters set the function to input the analog
reference received from the AI-A3 card and to adjust the gain and bias of these signals.
766
V/f
CL-V/f
OLV
CLV
AOLV
The drive will detect PGoH [Encoder (PG) Hardware Fault] if the value of this parameter is
smaller than the value of
, Sin θ is the single-track (phase B) output from the encoder and Cos θ
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communication speed between the PG-F3 option and the serial encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the analog reference used with AI-A3.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
(Range)
80%
(1 - 100%)
.
Default
(Range)
0
(0 - 2)
Default
(Range)
0
(0, 1)

Advertisement

Table of Contents
loading

Table of Contents