B9: Zero Servo - YASKAWA GA700 Series Technical Manual

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

No.
Name
(Hex.)
b8-28
Over Excitation Action
Selection
(0B8B)
Expert
b8-29
Energy Saving Priority
Selection
(0B8C)
b8-50
Standby Mode Selection
(0B0D)
b8-51
Standby Mode Wait
Time
(0B01)

b9: Zero Servo

No.
Name
(Hex.)
b9-01
Zero Servo Gain
(01DA)
b9-02
Zero Servo Completion
Window
(01DB)
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for excitation operation.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the priority of drive response between changes to the load or Energy-saving
control. Enable this to prioritize energy-saving control. Disable this to prioritize
tracking related to fast load changes, and prevent motor stall.
0 : Priority: Drive Response
1 : Priority: Energy Savings
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Standby Mode function.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time before turning off the electromagnetic contactor after the drive
stops.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness for the Zero Servo function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the range to trigger an output terminal set for "Zero Servo Complete" during Zero
Servo operation. Be sure to set the deviation from the Zero Servo start position.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.5 b: Application
Default
Ref.
(Range)
0
689
(0, 1)
0
689
(0, 1)
0
689
(0, 1)
600 s
690
(0 - 6000 s)
Default
Ref.
(Range)
5
691
(0 - 100)
10
691
(0 - 16383)
491