11.5 b: Application
No.
Name
(Hex.)
b3-24
Speed Search Method
Selection
(01C0)
b3-25
Speed Search Wait Time
(01C8)
Expert
b3-26
Direction Determination
Level
(01C7)
Expert
b3-27
Speed Search RUN/BB
Priority
(01C9)
Expert
b3-29
Speed Search Back-EMF
Threshold
(077C)
Expert
b3-31
Spd Search Current
Reference Lvl
(0BC0)
Expert
b3-32
Spd Search Current
Complete Lvl
(0BC1)
Expert
b3-33
Speed Search during Uv
Selection
(0B3F)
Expert
b3-35
Low Back EMF
Detection Level
(0BC3)
Expert
b3-36
High Back EMF
Detection Level
(0BC4)
Expert
b3-39
Regen Judgment Lv of
Spd Search
(1B8F)
Expert
b3-54
Search Time
(3123)
b3-55
Current Increment Time
(3124)
Expert
484
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Speed Search method when you start the motor or when you restore power after
a momentary power loss.
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], the default setting
changes when the setting for E9-01 [Motor Type Selection] and the drive model
change.
–E9-01 = 0 [Induction (IM)]
–2004 to 2313, 4002 to 4296: 1
–2360, 2415, 4371 to 4675: 2
–E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 1
• When you set A1-02 = 8 and E9-01 = 1 or 2, also set b3-24 = 1. If b3-24 = 2, the
drive will detect oPE08 [Parameter Selection Error].
• When you set b3-24, it will trigger the drive to initialize b3-14 [Bi-directional
Speed Search]. After you set b3-24, set b3-14.
1 : Speed Estimation
2 : Current Detection 2
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time the drive will wait to start the Speed Search Retry function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to find the motor rotation direction. Increase the value if the drive cannot
find the direction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the conditions necessary to start Speed Search.
0 : SS Only if RUN Applied Before BB
1 : SS Regardless of RUN/BB Sequence
V/f
CL-V/f
OLV
CLV
AOLV
Sets the induced voltage for motors that use Speed Search. The drive will start Speed
Search when the motor induced voltage level is the same as the setting value. Usually it
is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level that decreases the output current during Current Detection Speed
Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level that completes Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that starts Speed Search at start-up if the drive detects a Uv
[Undervoltage] when it receives a Run command.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Low Back EMF Detection Level. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the voltage level for Speed Search restart. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to determine the regenerative state during speed search. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will run Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will increase the current from zero current to the
setting value of b3-06 [Speed Estimation Current Level 1].
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Default
Ref.
(Range)
2
663
(1, 2)
0.5 s
664
(0.0 - 30.0 s)
1000
664
(40 to 60000)
0
664
(0, 1)
10%
664
(0 - 10%)
1.50
664
(1.50 - 3.50)
1.20
664
(0.00 - 1.49)
1
665
(0, 1)
10%
665
(5 - 50%)
0.970
665
(0.500 - 1.000)
15%
665
(0 - 50%)
400 ms
665
(10 - 2000 ms)
10 ms
666
(10 - 2000 ms)