n8-75: Medium Load Iq Level (low)
No.
Name
(Hex.)
n8-75
Medium Load Iq Level
(low)
(05C4)
Expert
Note:
• If n8-74 [Light Load Iq Level] > n8-75, the drive will detect oPE08 [Parameter Selection Error].
• The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Medium Load Id Current].
n8-77: Heavy Load Iq Level
No.
Name
(Hex.)
n8-77
Heavy Load Iq Level
(05CE)
Expert
Note:
The change is linear between n8-75 [Medium Load Iq Level (low)] and n8-77 and the level of the pull-in current from n8-78 [Medium
Load Id Current] to n8-49 [Heavy Load Id Current].
n8-78: Medium Load Id Current
No.
Name
(Hex.)
n8-78
Medium Load Id Current
(05F4)
Expert
n8-79: Pull-in Current @ Deceleration
No.
Name
(Hex.)
n8-79
Pull-in Current @
Deceleration
(05FE)
If overcurrent occurs during deceleration, slowly decrease the setting in 5% increments.
Note:
When n8-79 = 0, the drive will use the value set in n8-51 [Pull-in Current @ Acceleration].
n8-84: Polarity Detection Current
No.
Name
(Hex.)
n8-84
Polarity Detection Current
(02D3)
Expert
Note:
The drive automatically calculates this value when High Frequency Injection Auto-Tuning completes successfully.
WARNING! Sudden Movement Hazard. Make sure that the polarity is correct before you send a Run command. If the drive
incorrectly detects the polarity, the drive can rotate in the direction opposite of the Run command and cause serious injury or
death.
When you use a Yaskawa motor, check the motor nameplate for an "Si" value and set this parameter ≥ "Si × 2".
Consult the motor manufacturer for information about maximum setting values.
Find the Polarity of Magnetic Poles
When you start operation, the drive estimates the magnetic poles and finds the polarity of the magnetic poles.
When A1-02 = 7 [Control Method Selection = CLV/PM], the drive finds the polarity of the magnetic poles only at
the first startup.
Use U6-57 [PolePolarityDeterVal] to make sure that the drive correctly estimated the polarity of the magnetic
poles.
When you do High Frequency Injection Auto-Tuning, the drive automatically sets n8-84.
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-78 [Medium Load Id Current] to the percentage of load current (q-axis current) that you
will apply, where E5-03 [PM Motor Rated Current (FLA)] = a setting value of 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-49 [Heavy Load Id Current] to the percentage of load current (q-axis current) that you will
apply, where E5-03 [PM Motor Rated Current (FLA)] = a setting value of 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level of the pull-in current for mid-range loads.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the pull-in current that can flow during deceleration as a percentage of the E5-03 [PM Motor
Rated Current (FLA)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current that the drive uses to estimate the initial motor magnetic pole as a percentage
where E5-03 [PM Motor Rated Current (FLA)] = 100%.
12.10 n: Special Adjustment
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
50%
(0 - 255%)
Default
(Range)
90%
(0 - 255%)
Default
(Range)
0%
(0 - 255%)
Default
(Range)
50%
(0 - 200%)
Default
(Range)
100%
(0 - 150%)
12
939