Refer to the instruction manual included with the option card to install and set the option card.
Note:
If b1-01 = 3, but you did not connect a communications option card, oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the
keypad.
4 : Pulse Train Input
Use a pulse train signal from the pulse train input terminal RP to enter the frequency reference.
Do this procedure to make sure that the pulse train signal is operating correctly.
1. Set b1-01 = 4, H6-01 = 0 [Terminal RP Pulse Train Function = Frequency Reference].
2. Set H6-02 [Terminal RP Frequency Scaling] to the number of pulses that determine 100% of the frequency
reference.
3. Enter a pulse train signal on the terminal RP and make sure that the keypad shows a correct frequency
reference.
b1-02: Run Command Selection 1
No.
Name
(Hex.)
b1-02
Run Command Selection 1
(0181)
0 : Keypad
Use the keypad to enter the Run command.
You can use the JOG operation or the FWD/REV commands from the keypad.
Note:
The
on the keypad is on while keypad is the Run command source.
1 : Analog Input
Use the control circuit terminals to enter the Run command. Select the input method for the Run command with
an H1-xx parameter.
Set H1-xx = 0, 40 to 43 [3-Wire Sequence, Run Command (2-Wire Sequence)]. The default setting is 2-wire
sequence 1.
• 2-wire Sequence 1
This sequence has two input types: FWD/Stop and REV/Stop. Set A1-03 = 2220 [Initialize Parameters = 2-
Wire Initialization] to initialize the drive and set terminals S1 and S2 for a 2-wire sequence.
• 2-wire Sequence 2
This sequence has two input types: Run/Stop and FWD/REV.
• 3-Wire Sequence
This sequence has three input types: Run, Stop, and FWD/REV. Set A1-03 = 3330 [Initialize Parameters = 3-
Wire Initialization] to initialize the drive and set terminals S1, S2, and S5 for a 3-wire sequence.
2 : Memobus/Modbus Communications
Use MEMOBUS/Modbus communications to enter the Run command.
3 : Option PCB
Use a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If b1-02 = 3, but you did not connect a communications option card, oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the
keypad.
b1-03: Stopping Method Selection
No.
Name
(Hex.)
b1-03
Stopping Method Selection
(0182)
Note:
When A1-02 = 3, 4, 5, 6, 7, 8 [Control Method Selection = CLV, AOLV, OLV/PM, AOLV/PM, CLV/PM, EZOLV], the setting range is 0,
1, 3.
YASKAWA SIEPC71061705H GA700 Series Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the Run command.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor after removing a Run command or entering a Stop command.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.3 b: Application
Default
(Range)
1
(0 - 3)
Default
(Range)
0
(0 - 3, 9)
12
643