YASKAWA GA700 Series Technical Manual page 534

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

11.10 H: Terminal Functions
Setting Value
Function
16
Frequency Detection 4
17
Torque Detection 1 (N.
C.)
18
Torque Detection 2 (N.
O.)
19
Torque Detection 2 (N.
C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selected
1D
During Regeneration
1E
Executing Auto-Restart
1F
Motor Overload Alarm
(oL1)
20
Drive Overheat Pre-
Alarm (oH)
21
Safe Torque OFF
22
Mechanical Weakening
Detection
2F
Maintenance
Notification
30
During Torque Limit
31
During Speed Limit
32
In Speed Limit During
Trq Ctrl
534
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency > L4-03 [Speed Agree Detection Level(+/-)]. After the terminal
activates, the terminal stays activated until the output frequency is at the value of "L4-03 - L4-04".
Note:
• The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency > L4-03
OFF : The output frequency < "L4-03 - L4-04", or the output frequency ≤ L4-03
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-02 for
longer than the time set in L6-03 [Torque Detection Time 1].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for
longer than the time set in L6-06 [Torque Detection Time 2].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for
longer than the time set in L6-06 [Torque Detection Time 2].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops
switching and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when you select motor 2.
ON : Motor 2 Selected
OFF : Motor 1 Selected
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the Auto Restart function is trying to restart after a fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly
and when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects mechanical weakening.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when drive components are at their estimated maintenance period.
Tells you about the maintenance period for these items:
• IGBT
• Cooling Fan
• Capacitor
• Soft charge bypass relay
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the torque reference is the torque limit set with L7 parameters, H3-02, H3-06, or H3-
10 [MFAI Function Selection].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the speed limit is active.
V/f
CL-V/f
OLV
CLV
AOLV
The motor accelerates in the forward direction or the reverse direction after enabling torque control and the
externally input torque reference is disproportionate to the load. The output terminal activates when this speed is
not higher than a constant speed and the motor speed is at the speed limit. This does not include operation when the
drive is stopped.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Ref.
836
837
837
837
837
838
838
838
838
838
839
839
839
839
839
839
840

Advertisement

Table of Contents
loading