12.8 H: Terminal Functions
OFF : The drive is not in baseblock.
■
9: Frequency Reference from Keypad
Setting Value
Function
9
Frequency Reference from
Keypad
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
■
A: Run Command from Keypad
Setting Value
Function
A
Run Command Source
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
■
B: Torque Detection 1 (N.O.)
Setting Value
Function
B
Torque Detection 1 (N.O.)
ON : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque <
L6-02 for longer than the time set in L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
• Refer to
L6: Torque Detection on page 900
■
C: Frequency Reference Loss
Setting Value
Function
C
Frequency Reference Loss
Note:
Refer to "L4-05: Fref Loss Detection Selection" for more information.
■
D: Braking Resistor Fault
Setting Value
Function
D
Braking Resistor Fault
■
E: Fault
Setting Value
Function
E
Fault
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
■
F: Not Used
Setting Value
Function
F
Not Used
834
V/f
CL-V/f
OLV
CLV
AOLV
Shows the selected frequency reference source.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the selected Run command source.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects overtorque or undertorque.
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a loss of frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure signals from the PLC.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM