7.5 Minor Faults/Alarms
Code
Name
SToF
Safe Torque OFF
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code
Name
TiM
Keypad Time Not Set
Note:
• Parameter o4-24 [bAT Detection Selection] enables and disables TiM detection.
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
TrPC
IGBT Maintenance Time (90%)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
UL3
Undertorque Detection 1
Note:
• The drive detects this error if the drive output current is less than the level set in L6-02 for longer than L6-03.
• If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-01 [Torque Detection Selection 1].
Code
Name
UL4
Undertorque Detection 2
Note:
• The drive detects this error if the drive output current is less than the level set in L6-05 for longer than L6-06.
• If detected, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-04 [Torque Detection Selection 2].
Code
Name
UL5
Mechanical Weakening Detection 2
Note:
• If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-08.
Code
Name
Uv
Undervoltage
358
Causes
One of the two terminals H1-HC or H2-HC
received the Safe Disable input signal.
The Safe Disable input signal is wired incorrectly.
There is internal damage to one Safe Disable
channel.
Causes
You put a battery in the keypad, but you have not
set the date and time.
Causes
The IGBT is at 90% of its expected performance
life.
Causes
A fault occurred on the machine.
Example: There is a broken pulley belt.
The parameters are incorrect for the load.
Causes
A fault occurred on the machine.
Example: There is a broken pulley belt.
The parameters are incorrect for the load.
Causes
The drive detected undertorque as specified by the
conditions for mechanical weakening detection set
in L6-08 [Mechanical Fatigue Detect Select].
Causes
The drive input power voltage is changing too
much.
There is a phase loss in the drive input power.
There is loose wiring in the drive input power
terminals.
There was a loss of power.
The main circuit capacitors have become
unserviceable.
The drive input power transformer is too small and
voltage drops when the power is switched on.
Air inside the drive is too hot.
Possible Solutions
• Make sure that the Safe Disable signal is input from an
external source to terminals H1-HC or H2-HC.
• When the Safe Disable function is not in use, connect
terminals H1-HC and H2-HC.
Replace the board or the drive. For information about replacing
the control board, contact Yaskawa or your nearest sales
representative.
Possible Solutions
Set the date and time with the keypad.
Possible Solutions
Replace the IGBT or the drive. Contact Yaskawa or your nearest
sales representative for more information.
Possible Solutions
Examine the machine and remove the cause of the fault.
Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque
Detection Time 1] settings.
Possible Solutions
Examine the machine and remove the cause of the fault.
Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque
Detection Time 2] settings.
Possible Solutions
Examine the machine for deterioration.
Possible Solutions
• Examine the input power for problems.
• Make the drive input power stable.
• If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
Correct errors with the wiring for main circuit drive input power.
Tighten the terminal screws to the correct tightening torque.
Use a better power supply.
Examine the capacitor maintenance time in monitor U4-05
[CapacitorMaintenance]. If U4-05 is more than 90%, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
• Check for an alarm when a molded-case circuit breaker,
Leakage Breaker (ELCB, GFCI, or RCM/RCD) (with
overcurrent protective function), or magnetic contactor is ON.
• Check the capacity of the drive power supply transformer.
Check the ambient temperature of the drive.