YASKAWA GA700 Series Technical Manual page 950

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

12.11 o: Keypad-Related Settings
Drive Model
4009
4012
4018
4023
4031
4038
4044
4060
4075
4089
4103
o2-05: Home Mode Freq Ref Entry Mode
No.
Name
(Hex.)
o2-05
Home Mode Freq Ref Entry
Mode
(0509)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is
not necessary to push
the keypad to change the frequency reference value.
o2-06: Keypad Disconnect Detection
No.
Name
(Hex.)
o2-06
Keypad Disconnect
Detection
(050A)
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
• In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects oPr [Keypad Connection Fault], and the motor coasts to stop when the drive
detects a keypad disconnection.
o2-07: Keypad RUN Direction @ Power-up
No.
Name
(Hex.)
o2-07
Keypad RUN Direction @
Power-up
(0527)
This parameter is enabled in these conditions:
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
• In LOCAL Mode
950
o2-04 Setting
96
97
99
9A
9C
9D
9E
9F
A1
A2
A3
V/f
CL-V/f
OLV
Sets the function that makes it necessary to push
reference value while in Drive Mode.
. The drive keeps the frequency reference for 5 seconds after you use
V/f
CL-V/f
OLV
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive
or if you damage the cable while the keypad is the Run command source.
V/f
CL-V/f
OLV
Sets the direction of motor rotation when the drive is energized and the keypad is the Run
command source.
Drive Model
4140
4168
4208
4250
4296
4371
4389
4453
4568
4675
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
to use the keypad to change the frequency
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual
o2-04 Setting
A4
A5
A6
A7
A8
A9
AA
AC
AD
AE
Default
(Setting Range)
0
(0, 1)
and
on
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)

Advertisement

Table of Contents
loading

Table of Contents